86
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
1122..22
EEtthheerrnneett
The STS has an Ethernet port and cable. (For physical attachment see paragraph
). The
Ethernet cable must be physically attached to the customer network and STS Ethernet addresses set before
Modbus TCP/IP, SNMP, or SNTP Time Synchronization are configured.
The
Ethernet Settings
panel in the
Settings
screen (Figure 49) allows the operator to set an IP address if a
different address than the DHCP address is required.
•
Address
is the Ethernet IP address of the Switch, which can be set directly or by DHCP.
–
If the
Use DHCP
has a green check mark (√), the DHCP address will be used for the IP address in
Address
.
–
Use DHCP
icon has a red X, DHCP is not used to set the IP address. Enter an IP address in
Address
for the Switch.
•
Mask
to enter Ethernet IP mask address.
•
Gateway
to enter Ethernet Gateway.
•
MAC ID is set in the factory and cannot be changed.
•
Use DHCP
button:
–
(√): Use DHCP to assign IP address.
–
X: Do not use DHCP; use
Address
IP value.
•
Stat button: shows communications statistics (a service function)
•
Restart button: restarts the Monitor. On the ROI, the Mode of Operation must be set to
Redundant
so
that there is a backup transfer process during the restart.
NOTE:
The Monitor must be restarted when
Ethernet Settings
change.
1122..33
TTiim
mee S
Seettttiinnggss
Time stamps are important data for log entries and alarms. The STS clock should be synchronized with clocks
in other equipment to accurately diagnose problems affecting multiple systems. You can set the STS clock
manually or with the Time Synchronization feature.
1122..33..11 M
Maannuuaall TTiim
mee S
Seettttiinngg
To manually set the clock, enter a date and time in
Time Settings
on the
Settings
screen
.
Press the
Set
button, which will bring up the
Keyboard
Screen. Enter time and date.
1122..33..22 TTiim
mee S
Syynncchhrroonniizzaattiioonn S
Seettttiinnggss S
Sccrreeeenn ((S
SN
NTTP
P))
The Time Synchronization feature with SNTP requires the STS Ethernet connection.
Prerequisites:
1.
The
Ethernet Settings
on the
Settings
screen must be configured.
2.
The Ethernet port must be connected to a network with a reachable time server supporting SNTP.
3.
You must have the IP address of the time server. The time server could be a dedicated time server
possibly with a GPS receiver, a local computer running time server software, or a time server on the
Internet. You should preferably use a local time server. All equipment related to the STS should use the
same time server if they have access.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...