If an alarm of any type occurs, it triggers several notifications, according to your unit’s configuration:
•
It is listed on the
ALARM
screen as both an Active Alarm and Alarm History.
•
The alarm is listed in the
LOG
. (System can log up to 250 events).
•
If so configured, an audible alarm will sound at the unit’s Infinity 2 Monitor.
•
The Alarm section the screen banner is colored according to the highest active alarm severity and the
alarm, warning, or zero count in the banner is incremented.
•
If the affected sensor has a sensor symbol on the
HOME
screen 1-line, it is colored according to alarm
severity.
•
If analog, the corresponding analog sensor page will also have color-coded status information.
•
If digital, the corresponding digital sensor page will show the alarm active.
•
Transformer temperature alarms will show color-coded by severity on the
HOME
screen 1-line.
•
The Modbus Points List will provide alarm status.
•
If so configured, SNMP will send a trap indicating an active summary alarm.
•
If so configured, a relay summary alarm will activate.
66..44..22
A
Allaarrm
m S
Sccrreeeenn
Select the Alarm (center) section of the
HOME
screen banner to view the
Alarm
screen. The
Alarm
screen
can be toggled between showing active alarms and alarm history.
Active Alarm:
Alarms are placed on the active list when they occur and are automatically removed when the
alarm condition clears.
Alarm History:
All alarm events are recorded, that is, retained in the Alarm History list, when they become
active. To clear the Alarm History, select the garbage can icon. (You must be a logged-in user to clear the alarm
history.)
An alarm will never occur more than once on the Active or History list. However, if an alarm is raised multiple
times, each occurrence will be listed in the
Log
. See paragraph
.
Содержание PDI WaveStar Infinity 2
Страница 1: ...p n P 164001106 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Infinity 2 Monitoring System...
Страница 4: ......
Страница 10: ...x Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Safety...
Страница 60: ...50 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Setup...
Страница 76: ...66 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Maintenance...
Страница 78: ...P 16400110601 P 164001106 01...