Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
17
Power must be disconnected and locked out before installing and connecting CTs.
To measure current on panelboard branch circuits, install split-core CTs rated at 60A and matching cable
harnesses. CT installation has these steps:
1.
Run cable harnesses in the correct orientation from panelboards to JCOMM.
2.
Connect cable harnesses to JCOMM Connections Panel.
3.
Connect split-core CTs to the cable harnesses.
4.
Clip CTs over circuit wires in correct order.
44..55..11
R
Ruunn C
Caabbllee H
Haarrnneesssseess ttoo JJC
CO
OM
MM
M
Figure 8. Cable Harness Orientation
Typically, JCOMM cable harnesses are run from a top-mounted JCOMM. Run the cable harness to the
panelboard through a JCOMM a knockout so that cable harness CT connector #1 (J1) connects to the top of
the panelboard and #21(J21) to the bottom. Put a U-bend in the harness to orient the harness so that it
Содержание PDI JCOMM
Страница 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Страница 4: ......
Страница 8: ...viii Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 List of Figures...
Страница 10: ...x Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Страница 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Страница 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Страница 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Страница 50: ...P 16400110701 P 164001107 01...