SPECIFICATIONS
• Single Pole and 3-Way
• 15A, 120V AC 60 Hz – Incandescent, Magnetic Low Voltage, Magnetic Ballast
10A, 120V AC, 60 Hz – LED, Compact Fluorescent, Electronic Low Voltage, Electronic Ballast
8A, 277V AC, 60 Hz – Magnetic Low Voltage, Magnetic Ballast, LED, Compact Fluorescent,
Electronic Low Voltage, Electronic Ballast
1/2 HP, 120V AC, 60 Hz – Motor
•
NOTE
- A Ground Connection is required in the wallbox where the sensor will be installed.
DESCRIPTION
• This Sensor Wall Switch can replace a standard wall switch in any of the following applications:
• Single location – one Single Pole switch.
• Two location – one location is the sensor and the other location is a standard 3-way switch.
• Two location – replace both 3-Way switches with sensors.
• The OSP10M can interface with an external control Switchpack.
• The OSP10M turns on automatically when a person enters the room.
• Will automatically turn OFF lights after a selectable time delay.
• The selectable time delays are 5 seconds (Test Mode), 5 minutes (factory default), 15 minutes and 30 minutes.
• Includes a light level adjustment for daylight to prevent motion from turning ON the lights.
• A green LED indicates the load status and provides a momentary flash to indicate motion.
• The OSP10M relay connections are isolated. They may be wired to a load that is powered from a different
power source than the sensor power.
SPECIAL MODES
•
Reverse Mode:
The reverse mode is used when the lights must stay OFF in a room while motion is detected.
If the lights are ON, a double tap of the ON/OFF button will turn off the lights and put the device into the
Reverse Mode. This allows the lights to stay OFF as long as motion is detected. After the time delay is
finished the sensor operation goes back to normal.
•
Vacancy mode:
This mode may be selected to prevent motion from automatically turning on the lights.
Press and hold the ON/OFF button for 5 seconds until the indicator LED blinks. Release the button while the
LED is blinking. Repeat this procedure to restore normal operation.
•
Override Mode:
Turns off all motion sensing and allows the device to be used as a regular ON/OFF switch
or in the unlikely event of a failure of the motion sensor. Press and hold the ON/OFF button for 10 seconds
until the indicator LED blinks for the second time (the LED will also blink at the 5 second point). Release
the button while the LED is blinking. Repeat this procedure to restore normal operation.
•
Disable Manual Operation –
In this mode the sensor will function normally with automatic sensing,
however the sensor will not respond to pressing the ON/OFF button. This feature is enabled by
pressing and holding the ON/OFF button for 15 seconds until the LED indicator blinks for the third time
(the LED will also blink at the 5 second and 10 second point) and then releasing the button while the
LED is blinking. Repeat this procedure to restore normal operation.
INSTALLATION INSTRUCTIONS
WARNING:
•
Turn OFF circuit breaker or remove fuse(s) and verify that power is OFF before wiring.
• Never wire any electrical device with power turned ON. Wiring the device with the power on
is
unsafe and may cause permanent damage to the device and void the warranty.
• If you are unsure about any part of these instructions, or if the wiring does not match the
descriptions given, you should call a qualified electrician.
CAUTION:
• Must be installed and used in accordance with all applicable electrical codes.
• If a bare copper or green ground connection is not available in the wallbox, contact a quali-
fied
electrician for installation. Do not install without proper ground connections.
• Do not exceed maximum device ratings.
• For use ONLY with permanently installed fixtures of these types:
Incandescent/Halogen, Magnetic Low Voltage (MLV), Electronic Low Voltage
(ELV), Fluorescent, Compact Fluorescent, LED.
• May also be used with motors up to 1/2 HP
• To avoid overheating and possible damage to other equipment, do not use to control receptacles.
• Use only #14 or #12 copper wire with these devices.
• Make sure the controlled load (connected to Relay OUT) is rated to handle the volt-
age
connected to the Relay IN wire of the OSP10M
Installing OSP10M for single pole application
Refer to wiring diagram 1A and install the sensor properly by following the
described wire connections. Once all wires are connected, using the provided
wire nuts,
go to COMPLETING THE INSTALLATION
.
Installing OSP10M for Switchpack control
Refer to wiring diagram 1B and install the sensor properly by following the
described wire connections. Once all wires are connected, using the provided
wire nuts,
go to COMPLETING THE INSTALLATION
.
Installing OSP10M for 3-way applications
NOTE that the 3-way switch is NOT wired in the traditional 3-way manner.
Refer to either wiring diagram 2A or 2B and install the sensor properly by follow-
ing the described wire connections (The sensor may be placed at either end of
the
3-way circuit). Once all wires are connected, using the provided wire nuts,
go to
COMPLETING THE INSTALLATION
.
Installing OSP10M for 2 sensor applications
Refer to wiring diagram 3 and install the sensor properly by following the
described wire connections. Once all wires are connected, using the provided
wire nuts,
go to
COMPLETING THE INSTALLATION.
DIAGRAM 1A: SENSOR IN ONE LOCATION (NON-ISOLATED)
Light Fixture
White
Neutral
Ground
Bare
Green
3-Way
Blue
Black
Hot
Black
120/277V
Hot
Black
Relay OUT
Red
120/277V
Orange
Relay IN
0
15’
MAJOR MOTION
1000 SQ. FT.
36’
0
COVERAGE PATTERN
MINOR MOTION
300 SQ. FT.
8’
15’
8’
15’
DIAGRAM 1B: SENSOR AND SWITCHPACK CONTROL
Ground
Green
Red Relay out
Hot Black
Orange Relay in
Blue wire
Red wire
Switchpack control lines
First Location
Second Location
DIAGRAM 2A: SWITCH IN LOCATION WITH HOT WIRE
3-Way Switch
Hot
Black
120/277V
Hot
Black
120/277V
Black
3-Way
Blue
Neutral
Neutral
White
White
Light
Fixture
Black Traveler
Red Traveler
Red
Relay OUT
Ground
Bare
Green
Relay IN
Orange
Arrow Hart
Catalog # OSP10M Occupancy Sensor (Single Output)
ENGLISH
www.eaton.com
www.eaton.com/wiringdevices
EIS-0156-E (REV.A)