Eaton MTL 9493-PS-XXX Скачать руководство пользователя страница 1

MTL 9493-PS-XXX

intrinsically safe power supply

February 2016
INM MTL 9493-PS-XXX rev 1

Instruction manual

MTL intrinsic safety solutions

Содержание MTL 9493-PS-XXX

Страница 1: ...MTL 9493 PS XXX intrinsically safe power supply February 2016 INM MTL 9493 PS XXX rev 1 Instruction manual MTL intrinsic safety solutions...

Страница 2: ...ii INM 9493 PS XXX rev 1 This page left intentionally blank...

Страница 3: ...ction of equipment 10 4 3 Backplane mounting 10 4 3 1 Surface mounting with kit SMS01 12 4 3 2 T or G section DIN rail mounting with kit DMK01 12 4 4 Backplanes identification and tagging 12 4 4 1 Bac...

Страница 4: ...G These assemblies may not be used in explosion hazard area applications if they have been used previously in general electrical installations WARNING The responsibility for planning installation comm...

Страница 5: ...to each of the devices connected to its five ports PD Powered Device This adaptation is necessary due to restrictions for Hazardous Area use It is not implied that the device conforms to the 802 3af P...

Страница 6: ...circuited or overloaded This also minimises the power dissipation during the fault to a negligible level thus improving reliability 3 DIN RAIL INSTALLATION METHOD Hazardous area Safe area Figure 2 1...

Страница 7: ...nd dust and note the ambient temperature considerations given in Section 5 WARNING When mounted in a Zone 2 hazardous area the module must be protected by a suitably certified enclosure See the Specia...

Страница 8: ...d or replacement purposes Power conductors The removable power plugs are fitted with screw clamp terminals Note that the conductors should be between 14 and 24 AWG 1 6 and 0 5mm dia in size Plugs loca...

Страница 9: ...eck to make sure the bus length is correct for the number of modules involved 2 If the number of modules is less than the maximum number the chain will support cut off the surplus power plugs at the t...

Страница 10: ...e lower slot but only after insulating mounting blocks IMB57 are clamped to the DIN rail This may not be possible if for example trunking is fitted In this case fit offset earth rail bracket ERB570 se...

Страница 11: ...awing showing part numbers Figure 3 5 Mounting details Figure 3 6 IMB57 Insulating mounting block Figure 3 7 TAG57 Tagging strip 1m length Figure 3 8 MS010 DIN rail module spacers Figure 3 9 ETM7 Eart...

Страница 12: ...mounting blocks Snap out the perforated extension between the lugs on this mounting block if a continuous tagging strip is to be fitted see figure 3 4 b In lower position where at least 150mm clearanc...

Страница 13: ...MTL 9493 PS XXX power supplies using the accessories mentioned above The broken line boxes either side of the assembly represent cable trunking and the accompanying dimensions represent the minimum sp...

Страница 14: ...IES DIN rail 19 inch Earth rail Tagging Spare Surface T or G rack kit strip kit fuse pack SMS01 DMK01 ERK08 TSK08 FUS08 4 2 Protection of equipment When the power supply is mounted in a safe area ensu...

Страница 15: ...procedure T section 12 T section 12 G section 13 G section 13 Fixing Screws End stop 11 OR Figure 4 4 Mounting a backplane onto DIN rail Figure 4 5 Mounting end stops onto DIN rail Figure 4 6 Backplan...

Страница 16: ...6 Figure 4 4 h Locate the assemblies over the mounting feet and attach the screws 1 to the feet Figure 4 4 i For backplanes that are mounted in a vertical orientation attach one end stop 11 to the low...

Страница 17: ...ng strip Figure 4 9 Attaching an earth rail post Figure 4 10 Attaching earth rail terminals and rivets Figure 4 11 Power supply connections PSU A secondary supply can be connected in the same configur...

Страница 18: ...pply sources according to the terminal assignments shown in Figure 4 11 The maximum permissible wire size is 2 5mm2 14 AWG b Plug the power supply connectors into the base connectors on the backplanes...

Страница 19: ...rea power output plugs Haz 1 3 ia output 0ther models available Hazardous area power connectors Figure 4 14 Key elements of the MTL 9493 PS XXX power supply Figure 4 15 Fitting power supplies to backp...

Страница 20: ...EC Low Voltage Directive Region Europe ATEX International IECEx Authority CML CML Standard EN 60079 0 2012 EN 60079 11 2012 EN 60079 26 2006 IEC 60079 0 2011 IEC 60079 11 2011 IEC 60079 26 2006 Approv...

Страница 21: ...of those noted in the certification documentation and the product specification ii aggressive substances excessive dust moisture and other contaminants c This apparatus is intrinsically safe electric...

Страница 22: ...device is marked in accordance with the Directive and CE marked with the Notified Body Identification Number This information applies to products manufactured during or after the year 2010 Figure 8 1...

Страница 23: ...19 INM 9493 PS XXX rev 1 9 APPENDIX A DECLARATION OF CONFORMITY...

Страница 24: ...20 INM 9493 PS XXX rev 1 DECLARATION OF CONFORMITY continued...

Страница 25: ...21 INM 9493 PS XXX rev 1 This page left intentionally blank...

Страница 26: ...22 INM 9493 PS XXX rev 1 This page left intentionally blank...

Страница 27: ...23 INM 9493 PS XXX rev 1 This page left intentionally blank...

Страница 28: ...No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio...

Отзывы: