Control Circuit Devices M22-
SWD…
72
06/09 AWB2723-1613en
Programming
The various function elements have specific input/output
information that is processed in the programming system.
The meaning and scope are described in the following.
M22-SWD-K11
The function element has one input byte at its disposal.
Inputs
Byte 0:
NO1
NC1
7
6
5
4
3
2
1
0
-
P
-
F
-
-
NO1
NC1
Bit
Designation
Meaning
0
NC1 = Normally Close
0: Contact actuated
1: Contact not actuated
1
NO1 = Normally Open
0: Contact not actuated
1: Contact actuated
2
not used
-
3
not used
-
4
F = Failure
0: No diagnostic alarm
1: Diagnostics available
5
not used
-
6
P = Module present
0: Module not available
1: Module available
7
not used
-