Menvier40/100
Installation
Page 23
Figure 39 FSL Zone Wiring
– Control Unit
Figure 40 shows the wiring connections for FSL
zones on the EXP-W10 expander. Note that the
connections are different on the expander
compared with the control unit.
Zone 0
Zone 1
2K2 EOL
Wired Expander
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
100 Ohms
Z0
Z1
Z2
Z3
Z4
Figure 40 FSL Zone Wiring
– EXP-W10
The allowed values for Alarm Contact/End of Line
resistors are: 4k7/2k2. 1k0/1k0, 2k2/2k2, or
4k7/4k7.
Note: Use the same pair of values for ALL FSL
wired circuits on the control unit. Each wired
expander can use a different pair of resistor
values, but ALL circuits on an expander must
have the SAME values.
Figure 41 shows The wiring connections for FSL
zones on the EXP-WCC.
Zone 0
Zone 1
2K2 EOL
Wired Expander
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
100 Ohms
Figure 41 FSL Zone Wiring
– EXP-WCC
The allowed values for Alarm Contact/End of Line
are the same as for the EXP-W10.
Figure 42 shows the wiring connections for FSL
zones on a KEY-KPZ01. Note that the resistance
values shows are examples.
KEY-KPZ01
Zone 0
Zone 1
2K2 EOL
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
100 Ohms
Figure 42 Wiring FSL Zones on KEY-KPZ01
When programming select the FSL resistor values
for the control unit in
Installer Menu - System Options
- Wired Zone Type
. To select the resistor values for
a wired expander use
Installer Menu – Detectors
Devices – Wired Expanders - Edit Expander
.
If you wish to connect two or more detectors to a
FSL zone, Figure 43 shows the connections
required.
Figure 43 Wiring Two Detectors per Zone FSL.
Figure 44 shows an example of wiring double
doors with two door contacts to one FSL zone.
Each door contact is a reed switch, connected