Parameter menu (PAR)
83
Analog output (P4)
An analog voltage signal from 0 - +10 V is output at control signal
terminal 18. The maximum permissible load is 10 mA. Reference
potential is GND on control signal terminals 3 and 5.
In the factory setting, the voltage signal (0 - 10 V) is proportional
to the output frequency f-Out = 0 - f
max
(P6.4).
h
The output signal is not monitored by the frequency
inverter.
Figure 76:
Analog output AO
5
0...+10 V
AO
18
GND
<
10 mA
f-Out
-
+
PNU
ID
Access right
RUN
Value
Description
Factory setting
(P1.3)
P4.1
307
/
AO signal (Analog Output).
1
0
Deactivated
1
Output frequency f-Out = 0 – f
max
(P6.4)
2
Output current I
2
= 0 – I
N Motor
(P7.1)
3
Torque M
N
= 0 – 100 % (calculated value)
4
PID controller, output (0 - 100 %)
P4.2
310
/
AO, minimum value
1
0
0 V
1
2 V (live-zero)
P4.3
1456
/
AO, gain
100.00
Gain Factor: 0.00 - 200.00 %.
The maximum value set here always corresponds to the maximum
output voltage 10 V.
P4.4
1477
/
AO, filter time constant
0.10
0.01 - 10.00 s = Filter time constant for the analog output
voltage.