Parameters
04/10 MN04020001Z-EN
100
PID controller (P9)
The frequency inverters of the M-Max
TM
series are provided with
a PID controller that you activate with P9.1 = 1. The controller can
be deactivated via a digital input (DI6 in FS) P3.12 = 6.
h
PID control is superimposed on the frequency inverter
function. You should therefore set all of the frequency
inverter’s drive-related parameters, such as maximum
output frequency (motor speed), acceleration and
deceleration ramps (mechanical load, belts). Frequency
inverter and motor are process-integrated actuators. The
output frequency to the motor (which determines the
speed) is specified as manipulated variable from the PID
controller.
h
When the PID controller is activated, the setpoints and
actual values become process variables and are
normalized automatically into percentages (%). For
example, the specified setpoint (0 - 100 %) here is the
same as a volume flow (0 - 50 m3/h). The actual value
here is the volume flow (m3/h) from a suitable sensor,
which is evaluated again as a percentage (0 - 100 %).
If this process data is to be displayed in the physical
variable (m
3
/h), you can set the conversion with
parameter P9.19 (
a
“Display factor (P9.19)”).
PNU
ID
Access right
RUN
Value
Description
Factory setting
(P1.3)
P9.1
163
/
PID Controller
0
0
Deactivated
1
Activated for drive control.
2
Activated for external application.
P9.2
118
/
PID controllers, P amplification
100
Setting range: 0.0 - 1000 %
Proportional Gain (KP)
• Low values attenuate the control action.
• High values can cause oscillation.
P9.3
119
/
PID controller, I reset time
10.0
Setting range: 0.00 - 320.0 s
Integral time constant
P9.4
167
/
PID controller, setpoint input via operating unit
0.0
Setting range: 0.0 - 100.0 %
P9.5
332
/
PI controller, setpoint source
0
0
The setting range is limited by P6.3 (raised starting frequency) and
P6.4 (end frequency).
• Potentiometer (keypad)
• Frequency [Hz]
• Process variable [%] with P9.1 = 1
1
Fieldbus
2
AI1
3
AI2
P9.6
334
/
PID controller, actual value (PV)
2
0
Fieldbus
1
AI1 a
nd
S2, (
P2.1 = 0 (0 mA/0 V)
P2.1 = 1 (4 mA/2 V)
2
AI2
and
S3, (
P2.5 = 0 (0 mA/0 V)
P2.5 = 1 (4 mA/2 V)
P9.7
336
/
PID controller, actual value limiting, minimum
0.0
Setting range: 0.0 - 100.0 %
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...