background image

 

 

Effective May 2010

2C15999H02

05/10 AWA1230-2445

Auxiliary switch kit in

IZM low voltage circuit breakers

 warning

(1) Only qualified electrical persOnnel shOuld 

be permitted tO wOrk On the equipment.  

(2) always de-energize primary and  

secOndary circuits if a circuit breaker  

cannOt be remOved tO a safe wOrk lOcatiOn. 

(3) drawOut circuit breakers shOuld be 

levered (racked) Out tO the discOnnect  

pOsitiOn. 

(4) all circuit breakers shOuld be switched  

tO the Off pOsitiOn and mechanism springs 

discharged. 

failure tO fOllOw these steps fOr all  

prOcedures described in this instructiOn  

leaflet cOuld result in death, bOdily injury,  

Or prOperty damage.

 warning

the instructiOns cOntained in this awa and On 

prOduct labels have tO be fOllOwed. Observe 

the five safety rules: 

–   discOnnecting 

–   ensure that devices cannOt be  

  accidentally restarted 

–   verify isOlatiOn frOm the supply 

–   earthing and shOrt-circuiting 

–   cOvering Or prOviding barriers tO  

  adjacent live parts 

discOnnect the equipment frOm the supply. 

use Only authOrized spare parts in the repair 

Of the equipment. the specified maintenance 

intervals as well as the instructiOns fOr 

repair and exchange must be strictly adhered 

tO prevent injury tO persOnnel and damage tO 

the switchbOard.

Section 1: General information

An auxiliary switch is an optional device providing 

remote electrical indication if the circuit breaker is 

open or closed. Up to three auxiliary switches can 

be mounted in the circuit breaker. Each switch has 

two normally open (“A”) and two normally closed 

(“B”) contacts for a total of 12 available contacts. 

Section 2: Installation of the 

auxiliary switch

To install the auxiliary switch, proceed with the  

following five steps:

Step 1: 

Remove the front cover by unscrewing 

the hex head captive bolts (four for three-pole, 

six for four-pole) that join the cover to the breaker 

housing using a 10 mm 1/4-inch drive socket. 

Then hold the charge handle down approximately 

45 degrees to pull off the cover. 

Step 2: 

Place the appropriate label on the 

front cover nameplate space located under 

“Accessories.”

Figure 1. Steps 1 and 2

Label

Bolt

Отзывы: