background image

4

Instruction Booklet 

IB022003EN

Effective April 2018
Revision #3

Instructions for installation, operation, and

maintenance of Type MVS-ND, metal-enclosed

switchgear assemblies: 4.76 kV or 15.0 kV class

EATON 

www.eaton.com

Read and understand these instructions before attempting 

installation, operation, or maintenance of this equipment . This 

equipment must be installed and serviced only by qualified electrical 

personnel . Retain this document for future use .

 WARNING

HAZARD OF ELECTRICAL SHOCK OR BURN. OPERATING THE SWITCHGEAR 

ASSEMBLY OUTSIDE OF ITS RATINGS MAY CAUSE FAILURE RESULTING 

IN PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH. THE 

SWITCHGEAR ASSEMBLY MUST BE OPERATED WITHIN ITS NAMEPLATE 

RATINGS.

 WARNING

HAZARDS OF ARC FLASH, ARC BLAST, AND ELECTRIC SHOCK EXIST  

WHEN THIS EQUIPMENT IS ENERGIZED, WHICH MAY LEAD TO DEATH  

OR SEVERE INJURY. 

 

ALL WORK ASSOCIATED WITH THIS ELECTRICAL EQUIPMENT MUST BE 

PERFORMED ONLY BY QUALIFIED PERSONNEL AS DEFINED IN NFPA-70. 

CONSULT NFPA-70E, OSHA, AND ANY OTHER APPLICABLE REGULATION 

PERTAINING TO OPERATOR SAFETY PRIOR TO SERVICING EQUIPMENT. 

THE QUALIFIED PERSONNEL MUST FOLLOW ALL APPLICABLE PERSONAL 

PROTECTIVE EQUIPMENT REQUIREMENTS. 

 

DO NOT ATTEMPT ANY WORK ON THIS EQUIPMENT SUCH AS INSTALLING 

COMPONENTS, PERFORMING ANY EXAMINATIONS, PERFORMING  

ANY ADJUSTMENTS, PERFORMING ANY SERVICING, OR PERFORMING 

ANY MAINTENANCE WHILE IT IS ENERGIZED. BEFORE PERFORMING ANY 

WORK, FOLLOW ALL APPROPRIATE HAZARD ASSESSMENT AND ENERGY 

CONTROL PRECAUTIONS AND PROCEDURES. 

 

VERIFY NO VOLTAGES ARE PRESENT ON ALL INCOMING AND OUTGOING 

CONDUCTORS, AND ANY ENERGY SOURCES CONTAINED WITHIN THE 

EQUIPMENT PRIOR TO SERVICING, THEN GROUND (CONNECT TO EARTH) 

ALL INCOMING AND OUTGOING CONDUCTORS ATTACHED TO THIS 

EQUIPMENT AND TO ANY INTERNAL ENERGY SOURCES.

 DANGER

ALL APPLICABLE SAFETY CODES, SAFETY STANDARDS, AND SAFETY 

REGULATIONS MUST BE ADHERED TO WHEN INSTALLING, OPERATING, OR 

MAINTAINING THIS EQUIPMENT.

Introduction

Purpose

This instruction book is expressly intended to cover the installation, 

operation, and maintenance of medium voltage switch (type MVS-

ND) metal-enclosed switchgear . It is not encompassing of all possible 

contingencies, variations, and details that may arise during installation, 

operation, or maintenance of this equipment .
If further information is desired by the purchaser regarding this 

particular installation or application information, contact the local 

Eaton sales office, see the appropriate section of Eaton’s Consulting 

Application Guide, and review the appropriate industry standards . 

Description and application

The type MVS-ND metal-enclosed switchgear assemblies consists 

of one or more vertical sections of metal-enclosed switchgear as 

defined in industry standard American National Standards Institute/

Institute of Electrical and Electronic Engineers (ANSI/IEEE

T

C37 .20 .3 . Typically, each vertical section contains an air insulated, 

three-pole, gang-operated, quick-make, quick-break, load interrupter 

switch . It can be applied in combination with power fuses and many 

other protective devices to provide safe, economical switching and 

overcurrent protection where infrequent disconnecting means  

is required .

Documentation references

For receiving, handling, storing and installation instructions: 

IB022014EN .
For MVS-ND mounting to a foundation: Job Floor plan Document .
Refer to the customer drawing package documentation for order 

specific information . For further information on installation and 

application, refer to the applicable descriptive bulletins, publications, 

and/or industry standards . Download Eaton information from  

www .eaton .com .

Eaton contact information

For additional information about Eaton products please call  

1-800-525-2000 or log onto www .eaton .com . Additional medium 

voltage switchgear information regarding Pricing/Aftermarket, 

Customer Service, Engineering/Technical Information, or Warranty, 

can be found by calling 1-800-345-4072 .

Eaton Electrical Services and Systems (EESS) can be reached at 

1-800-498-2678 .

If further information is desired regarding this particular installation 

or application information, contact the local Eaton sales office, 

reference Eaton’s Consulting Application Guide, or the appropriate 

industry standards .

Terminology

Metal-enclosed load interrupter switchgear

This is an assembly of metal vertical sections as defined in  

ANSI/IEEE C37 .20 .3 .

Load interrupter switch

The basic switching and fault-closing device used in metal-enclosed, 

load interrupter switchgear .

Fuse

A device used in conjunction with a load interrupter switch to 

provide overcurrent and short-circuit protection .

Содержание Indoor MVS-ND

Страница 1: ...VS ND switchgear bolt tightness for bus connections 13 MVS ND switchgear field taping procedure 5 15 kV 14 Effective April 2018 Revision 3 Instruction Booklet IB022003EN Instructions for installation operation and maintenance of Type MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class Indoor MVS ND Switchgear Assembly Outdoor MVS ND Switchgear Assembly ...

Страница 2: ...uction Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com ...

Страница 3: ...contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HE...

Страница 4: ...hat may arise during installation operation or maintenance of this equipment If further information is desired by the purchaser regarding this particular installation or application information contact the local Eaton sales office see the appropriate section of Eaton s Consulting Application Guide and review the appropriate industry standards Description and application The type MVS ND metal enclo...

Страница 5: ...S ND switchgear assembly is securely fastened to a true and level surface according to the floor plan of the customer drawings 6 Always be sure that all hardware is in place and secured by tightening or using safety fasteners before putting an MVS ND switch into operation See Duplex switchgear configuration on Page 13 7 Confirm that all arc chutes and barriers are installed 8 Confirm that no tools...

Страница 6: ...eceiving handling storing and installation of the equipment please reference the Instructions for receiving handling storing and installation of medium voltage switchgear in addition to customer drawing package Refer to shipping list for location of the bus hardware and all other joining and installation material Floor requirements The finished foundation surface shall be flat and level within 0 0...

Страница 7: ...will face the transformer to the matching holes in the transformer case Minor misalignment may be corrected with a tapered guiding rod of some kind Insert the hardware and tighten Use extreme caution in moving the MVS ND switchgear to prevent damage Outdoor throat connection liquid filled transformers Step 1 Remove the sealing ring flange from MVS ND switchgear throat and set it aside Step 2 The s...

Страница 8: ...on For outgoing circuits the terminals are beneath the switch Each terminal pad has a two hole pattern suitable for either a single hole terminal or a terminal with a two hole National Electrical Manufacturers Association NEMA drilling pattern The terminal lugs for the cable if purchased with the switchgear will be bolted to the switchgear terminals If the terminal lugs are not there then they are...

Страница 9: ...N SOURCES CONSULT YOUR SAFETY DEPARTMENT BEFORE USING Securing MVS ND switchgear assemblies to foundations If the switchgear assembly was purchased for seismic applications follow the instructions on the specific drawings provided for the switchgear assembly that address the anchoring details Another drawing addresses the load bearing requirements Indoor or outdoor vertical sections are secured us...

Страница 10: ...OVED CLEANERS FOR THIS EQUIPMENT m CAUTION ISOPROPYL ALCOHOL IS FLAMMABLE PROVIDE ADEQUATE VENTILATION AND KEEP AWAY FROM FLAMES AND OTHER IGNITION SOURCES CONSULT YOUR SAFETY DEPARTMENT BEFORE USING Step 4 A final thorough inspection should be made to ensure that no tools or other objects are accidentally left inside the enclosure m WARNING DEFEATING OR DISENGAGING SAFETY INTERLOCKS ON AN MVS ND ...

Страница 11: ... any dust or dirt that may have accumulated inside each switchgear vertical section paying close attention to insulators and insulating material If the bus is insulated see Electrical parts and insulation check and cleaning for cleaning procedures Insulation and conductor maintenance Insulated bus coverings made from NORYL Insulated bus coverings are made from NORYL a high performance engineering ...

Страница 12: ...HGEAR ASSEMBLY FROM ALL POWER SOURCES PRIOR TO INSPECTION MAY RESULT IN SEVERE INJURY OR DEATH THE SWITCHGEAR ASSEMBLY MUST BE COMPLETELY DISCONNECTED FROM ALL POWER SOURCES AND GROUNDED BEFORE PERFORMING ANY INSPECTION m WARNING WHEN ACCESSING FUSES FAILURE TO ASSURE THAT THE FUSES ARE DE ENERGIZED MAY RESULT IN EQUIPMENT DAMAGE BODILY INJURY OR DEATH MAKE SURE THAT ALL POWER SOURCES ARE DE ENERG...

Страница 13: ...d Each of the locks is keyed alike and only one key must be available to operating personnel Since the key is retained in its lock when a switch is closed or when a door is opened two things are assured Only one switch may be closed at a time to prevent paralleling of incoming lines Both switches must be locked in the open position to unlock either main door preventing access to energized load sid...

Страница 14: ... tape material Trade name Scotch 130C for all cable termination insulation Refer to 3M s taping method instructions Tape Method for Insulating Bus Bar Connections 5 35 kV to Meet ANSI C37 20 Requirements for installation techniques when using this tape Figure 8 DWG NO MODEL REV SHEET OF TITLE ALL REV NOTES LISTED ON SHT 1 REV MODEL FILENAME T BLK REV 4 C 7819C35 2 2 3 JOINT TAPING THRU JOINTS WITH...

Страница 15: ... THE INSULATION ENDS METHODS GENERAL 1 ELONGATE INSULATING TAPE 10 TO 25 PERCENT DURING APPLICATION TO INSURE A SMOOTH TIGHT FIT ON PADS ELONGATE CORNERS ONLY 2 SHOULD A TAPE ROLL EXPIRE START THE NEW ROLL BY OVERLAPPING THE PREVIOUS END BY 5 TURN T JOINTS WITH HARDWARE 1 CLEAN AREA OF DIRT AND FOREIGN MATTER 2 WIPE PREINSULATION WITH ISOPROPYL ALCOHOL IF NECESSARY 3 APPLY FILLER OVER BARE CONDUCT...

Страница 16: ...lead must be carried through the Zero Sequence current transformer and solid ly ground ed on the load sid e of the ct as shown Use 6 wire with 600V insulation Power Cables Cond uit when used Cable connections to switchgear terminals when used with Insulated Pothead Cond uit must be terminated and solid ly ground ed on the load sid e of the current transformer Zero Sequence transformer Electrical j...

Страница 17: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Страница 18: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Страница 19: ...on Booklet IB022003EN Effective April 2018 Revision 3 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class EATON www eaton com Notes N ...

Страница 20: ...ved Printed in USA Publication No IB022003EN TBG001292 April 2018 Eaton is a registered trademark All other trademarks are property of their respective owners Instruction Booklet IB022003EN Effective April 2018 Instructions for installation operation and maintenance ofType MVS ND metal enclosed switchgear assemblies 4 76 kV or 15 0 kV class ...

Отзывы: