background image

Standard Fitting

Double Sided Legend Fitting

Safe Operation

1. Check the rating label for voltage and frequency before connecting this luminaire to the electrical 
    supply.
2. Ensure that the mains supply is switched off when working on this luminaire, whether installing or 
    carrying out any other servicing.
3. To prevent damage to driver, do not mix with conventional magnetic ballasts on the same electrical 
    circuit.
4. Where use in more onerous situations is required, e.g. In part-completed buildings before “drying-out” is 
    completed, or areas where ambient temperatures are outside the normal temperature range, then 
    consult our Sales Office.
5. Ensure the fixing is adequate for the luminaire weight.
6. The change mode of operation from mains to emergency is automatically changed to emergency mode by the 
    integral PCB control gear

Servicing and Disposal 

1. At commissioning and handing over of installation ensure that a copy of these instructions is presented  
    to the authority responsible for the operation and maintenance of the luminaries.
2. Servicing, e.g. cleaning, must only be carried out after the electricity supply has been switched off.  It 
    must not be assumed that luminaries with lamps not lit are switched off-always check before servicing.
3. Cleaning should be carried out at regular intervals to ensure that dirt does not accumulate to an extent   
    that will impair the thermal safety or optical performance of the luminaire.  Regular cleaning will also 
    ensure that the optical performance of the luminaries is maintained.
4. Avoid touching the LED. To clean - Blow surface with either dry air or nitrogen gas.
5. At the end of life the luminaire is classed as WEEE under directive 2002/96/EC and should be disposed 
    of in accordance with local legislation.

Battery Life

Performance of the luminaire is dependent on the use of the correct type of high temperature Nickel Cadium 
battery.

o

Battery life may be impaired if the luminaire is mounted in an ambient temperature greater than 25 C. Store the 

o

o

luminaire or battery between O C and 25 C. Replace with high temperature Nickel Cadium battery to the 
manufacturer's recommended part number. Take care not to damage the sleeving. The battery should be replaced 
when the rated duration is no longer achieved.

Warning: 

When disposing of the battery do not pierce, incinerate or short circuit. The battery should be disposed 

of in accordance with recognised disposal methods.

Note: The LEDs are non-replaceable but the batteries can be replaced by a competent person.

Luminaire Cleaning

End of Life and Components Disposal

WEEE

IP65

 Product luminaires comply with EN60598-2-22 and are suitable for use in normal interior and exterior conditions,                    

o

o

 For self contained variants - This luminaire has an ambient temperature range of -5 C to 25 C

o

o

 For slave variants - This luminaire has an ambient temperature range of -15 C to 40 C

Instruction Leaflet

K905V7

i-P65

June 2017

K905V7

Eaton

 

Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB

Sales 
    

T: +44 (0)1302 303303 
F: +44 (0)1302 367155 
E: [email protected]

General 
    

+44 (0)1302 321541
+44 (0)1302 303220
[email protected]

International Sales 
    

+44 (0)1302 303250
+44 (0)1302 303251
[email protected]

Instruction Manual - K905V7