background image

Before You Begin 

i-on30EX/EXD 

Page 14 

Table 1. Voltage Drop 

Current 
Drawn 

Cable Length (Standard 7/0.2 alarm cable) 

 

10m 

20m 

30m 

40m 

50m 

60m 

70m 

80m 

90m 

100m 

60mA 

0.10V 

0.19V 

0.29V 

0.38V 

0.48V 

0.58V 

0.67V 

0.77V 

0.86V 

0.96V 

80mA 

0.13V 

0.26V 

0.38V 

0.51V 

0.64V 

0.79V 

0.90V 

1.02V 

1.15V 

1.28V 

100mA 

0.16V 

0.32V 

0.48V 

0.64V 

0.80V 

0.96V 

1.12V 

1.28V 

1.44V 

1.60V 

120mA 

0.19V 

0.38V 

0.58V 

0.79V 

0.96V 

1.15V 

1.34V 

1.54V 

1.74V 

1.92V 

140mA 

0.22V 

0.45V 

0.67V 

0.90V 

1.12V 

1.34V 

1.57V 

1.79V 

2.02V 

2.24V 

160mA 

0.26V 

0.51V 

0.77V 

1.02V 

1.28V 

1.54V 

1.79V 

2.05V 

2.30V 

2.56V 

180mA 

0.29V 

0.58V 

0.86V 

1.15V 

1.44V 

1.73V 

2.02V 

2.30V 

2.59V 

2.88V 

200mA 

0.32V 

0.64V 

0.96V 

1.28V 

1.60V 

1.92V 

2.24V 

2.56V 

2.88V 

3.20V 

220mA 

0.35V 

0.70V 

1.06V 

1.41V 

1.76V 

2.11V 

2.46V 

2.82V 

3.17V 

3.52V 

240mA 

0.38V 

0.79V 

1.15V 

1.54V 

1.92V 

2.30V 

2.69V 

3.07V 

3.46V 

3.84V 

260mA 

0.42V 

0.83V 

1.25V 

1.66V 

2.08V 

2.50V 

2.91V 

3.33V 

3.74V 

4.16V 

280mA 

0.45V 

0.90V 

1.34V 

1.79V 

2.24V 

2.69V 

3.14V 

3.58V 

4.03V 

4.48V 

300mA 

0.48V 

0.96V 

1.44V 

1.92V 

2.40V 

2.88V 

3.36V 

3.84V 

4.32V 

4.80V 

320mA 

0.51V 

1.02V 

1.55V 

2.05V 

2.56V 

3.07V 

3.58V 

4.10V 

4.61V 

5.12V 

340mA 

0.54V 

1.09V 

1.63V 

2.18V 

2.72V 

3.26V 

3.81V 

4.35V 

4.90V 

5.44V 

360mA 

0.58V 

1.15V 

1.73V 

2.30V 

2.88V 

3.46V 

4.03V 

4.61V 

5.18V 

5.76V 

380mA 

0.61V 

1.22V 

1.82V 

2.43V 

3.04V 

3.65V 

4.26V 

4.86V 

5.47V 

6.08V 

400mA 

0.64V 

1.28V 

1.92V 

2.56V 

3.20V 

3.84V 

4.48V 

5.12V 

5.76V 

6.40V 

Reducing Voltage Drop - Method 1: 

Double up the supply connections (12V and 0V), 
which will halve the resistance on each core and 
therefore halve the voltage drop. When using 
Table 1 to calculate the expected voltage drop, 
simply divide the voltage drop for a single core by 
two. 

Reducing Voltage Drop - Method 2: 

Supply the detection devices from the Aux output 
on separate cores. This is the preferred method of 
reducing voltage drop as detectors generally 
operate at lower voltages (9.5V). When using this 
method, the bus cable must have at least two 
spare cores.  

Remote Power Supplies 

When you cannot reduce voltage drops by 
method 1 or 2, or the demand on the control unit 
power supply exceeds its capacity (see Technical 
Specifications 

–page 35), you should install one or 

more remote power supplies. The supply must 
have a "floating zero Volt rail" if connected to the 
bus, otherwise an earth fault will occur. 

Eaton’s 

Security Business recommends the EXP-PSU. 
When installing a remote power supply, fit it close 
to the equipment it is powering. 

Figure 18 shows the recommended method of 
connecting a remote power supply. 

 

Figure 18. Connecting Remote Power Supply Units 

Содержание i-on30EX

Страница 1: ...i on30EX i on30EXD Security System Installation Guide Issue 6...

Страница 2: ...erting you to potential problems or hazards Each of these are marked by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not...

Страница 3: ...re Closed Circuit Connections 20 Fully Supervised Loop Connections 20 Step 7 Connect Wired Outputs 22 Control Unit Wired Outputs 22 Wired External Sounders Optional 22 Wired Outputs on Expanders 22 Wi...

Страница 4: ...i on30EX EXD Page iv This page is intentionally blank...

Страница 5: ...grammable output and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders The range includes a door contact universal transmitter a pas...

Страница 6: ...cable The Installer Menu allows you to specify all the operating parameters for an individual installation If you wish you can also connect a PC or laptop to the mini USB port on the control unit PCB...

Страница 7: ...ll affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more infor...

Страница 8: ...poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the i on30EX its expanders and keypads have been tested for Electromagnetic Compatibility EMC However when handling...

Страница 9: ...t 1 Connectors for system bus 2 Zone output and Aux power connectors 3 Plug by output connectors 4 Tamper switch 5 ADSL filter pins i on30EXD only 6 On board communicator connections i on30EXD only 7...

Страница 10: ...XD Page 6 1 Built in communicator telephone line connector i on30EXD only 2 Siren and strobe 3 Loudspeaker 4 Bus cable connector 5 Output transistorised 6 Aux power 7 Wired zone connectors Figure 3 Co...

Страница 11: ...To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing...

Страница 12: ...to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 8 Gently swing the lower side of the front out from...

Страница 13: ...inals for zones 4 Sounder volume control 5 Connector for data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used in i onEX control units 6b LED functions and RS48...

Страница 14: ...aker connectors 19 Outputs Figure 14 EXP W10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper s...

Страница 15: ...sable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Loud...

Страница 16: ...ent drawn from the Aux terminals 12V must be included in the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an...

Страница 17: ...a star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 17 If required fit the termination jumper at the devices o...

Страница 18: ...360mA 0 58V 1 15V 1 73V 2 30V 2 88V 3 46V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Re...

Страница 19: ...and location for the user Out of sight of potential intruders Do NOT site the keypad s Next to electronic equipment particularly computers photocopiers or other radio equipment CAT 5 data lines or ind...

Страница 20: ...s You can set the function of the backlights in either of two ways a Use the Installer Menu Detectors Devices Wired Keypads Edit Keypad Keypad n Backlight option See the Engineering Guide for more det...

Страница 21: ...on key will glow for 20 seconds after the last press this may be useful when the keypad is placed in bedrooms that should be completely dark at night MENU STATUS OK LED 4 Leave local programming mode...

Страница 22: ...fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the cable Figure 23 Opening External Prox Reader Figure...

Страница 23: ...peakers During normal operation loudspeakers on expanders repeat setting and entry tones for the partition that the expander is allocated to During an alarm the loudspeakers repeat alarm tones Each lo...

Страница 24: ...ne Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL detectors to each pair of zone terminals To specify the zone wiring type use the Instal...

Страница 25: ...on a KEY KPZ01 Note that the resistance values shows are examples Figure 35 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System...

Страница 26: ...minal on the control unit see item 10 in Figure 3 as either CC or FSL Use Installer Menu System Options Panel Tamper Rtn By default the terminal is CC If you program the TR terminal as FSL then make s...

Страница 27: ...any other FSL resistor combinations CC wiring Eaton s Security Business does NOT recommend that you use CC wiring for this application The maximum length of wire allowable is only 6m Instead Eaton s...

Страница 28: ...PABX exchanges with or without secondary proceed indication Note The built in communicator is not suitable for connection as an extension to a pay phone or to 1 1 carrier systems Approval The built i...

Страница 29: ...nal Installer after 14 days written notice to the authorised maintainer To connect the telephone line see Figure 45 i Using a two core telephone cable strip off 5mm and feed the cable through one of t...

Страница 30: ...hen the fault is absent Tell Back Input This input is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tamper The communicator...

Страница 31: ...rt pause the keypad gives a confirmation tone The display briefly shows the bus address of the keypad If there are no other keypads connected to the bus it should be b1 d51 bus 1 device 51 Keypads tak...

Страница 32: ...flashes a second Each of these sequences has the following meaning No Flashes Meaning One Communication with control unit over bus is OK Two No communication over the bus in the last 10 seconds Three...

Страница 33: ...trying to set the system from a keypad will see the message Installer on Site All HUAs including radio HUAs fire alarm zones 24 hour zones and tampers are disabled If you have logged into the system...

Страница 34: ...ctory default options without defaulting the user and installer access codes then 1 From the Installer Menu select System Options Restore Defaults Factory Defaults The display shows 2 EITHER Press to...

Страница 35: ...ed description Note make sure that you allocate keypads correctly to partitions For more information see Assigning Wired Keypads to Partitions in the i on Range Engineering Guide Assemble and close th...

Страница 36: ...er Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation UK Confirmation Mode Basic...

Страница 37: ...is disabled 18 Appears only if Report Mode Fast Format AND Confirmation Mode Basic 19 Shows None on i on30EXD 20 Must be activated by a Eaton s Security Business External Support Manager 21 Appears o...

Страница 38: ...r you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you ca...

Страница 39: ...y available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply frequency User Codes 50 plus installer code Remote controls 50 one...

Страница 40: ...h sealed lead acid not supplied Low battery fault at 12V Aux power output fault at 9V Deep discharge protection at 10 0 5V Serviceable components Mains fuse 250mA T Standby time See Power Availability...

Страница 41: ...3rEUR 00 Pet tolerant PIR 714rEUR 00 PIR Transmitter Small case 720rEUR 00 Smoke Detector Transmitter 734rEUR 00 01 CC FSL Door Contact Transmitter white 734rEUR 05 06 CC FSL Door Contact Transmitter...

Страница 42: ...i on30EX EXD Page 38 NOTES...

Страница 43: ...i on30EX EXD Page 39 NOTES...

Страница 44: ...EXD Page 40 Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 12435139 21 1...

Отзывы: