Eaton GFCI Скачать руководство пользователя страница 1

1. What is a GFCI?

A GFCI receptacle is different from  

conventional receptacles. In the event of  

a ground fault, a GFCI will trip and  

quickly stop the flow of electricity to  

prevent serious injury.

Definition of a ground fault: 

Instead of following its normal safe  

path, electricity passes through a  

person’s body to reach the ground. For  

example, a defective appliance can cause  

a ground fault.

A GFCI receptacle does not protect  

against circuit overloads, short circuits,  

or shocks. For example, you can still be 

shocked if you touch bare wires while  

standing on a non-conducting surface,  

such as a wood floor.

3. Should you install it?

Installing a GFCI receptacle can be more  

complicated than installing a conventional  

receptacle. 

Make sure that you:

• Understand basic wiring principles  

   and techniques

• Can interpret wiring diagrams

• Have circuit wiring experience

• Are prepared to take a few minutes to

   test your work, making sure that you

   have wired the GFCI receptacle 

   correctly.

4. LINE vs. LOAD

A cable consists of 2 or 3 wires.

LINE cable: 

Delivers power from the service panel (breaker 

panel or fuse box) to the GFCI. If there is only 

one cable entering the electrical box, it is the 

LINE cable. This cable should be connected to 

the GFCI’s LINE terminals only. 

LOAD cable: 

Delivers power from the GFCI to another  

receptacle in the circuit. This cable should be 

connected to the GFCI’s LOAD terminals only. 

The LOAD terminals are under the yellow  

sticker. Do not remove the sticker at this time.

5. Turn the power OFF

Plug an electrical device, such as a lamp  

or radio, into the receptacle on which you are 

working. Turn the lamp or radio on. Then, go to 

the service panel. Find the breaker or fuse that 

protects that receptacle. Place the breaker in 

the OFF position or completely remove the fuse. 

The lamp or radio must turn OFF.

6. Identify cables/wires

Important: 

Do not install the GFCI receptacle in an  

electrical box containing (a) more than 4  

wires (not including the grounding wires) 

or (b) cables with more than two wires (not 

including the grounding wire). Contact a  

qualified electrician if either (a) or (b) is true.

If you are replacing an old receptacle,  

pull it out of the electrical box without  

disconnecting the wires. 

• If you see one cable (2-3 wires), it is the  

   LINE cable. The receptacle is probably in  

   position C (see diagram to the right). Remove 

   the receptacle and go to step 7A. 

• If you see two cables (4-6 wires), follow

   the procedure to the right. The receptacle

   is probably in position A or B (see diagram  

   to the right).

Procedure: box with two cables (4-6 wires) 

(a) Detach one cable’s white and hot wires from 

the receptacle and cap each one separately 

with a wire connector. Make sure that they are 

from the same cable.

(b) Re-install the receptacle in the electrical 

box, attach the faceplate, then turn the power 

ON at the service panel.  

(c) Determine if power is flowing to the  

receptacle. If so, the capped wires are the 

LOAD wires. If not, the capped wires are the 

LINE wires. 

(d) Turn the power OFF at the service panel, 

label the LINE and LOAD wires, then remove 

the receptacle. 

(e) Go to step 7B.

2. The GFCI’s features

•  To prevent severe shock or electrocution,  

  always turn the power OFF at the  

  service panel before working with  

 wiring.
•  Use this GFCI receptacle with copper  

  or copper-clad wire. Do not use it with  

  aluminum wire.
•  Do not install this GFCI receptacle on  

  a circuit that powers life support  

  equipment because if the GFCI trips it  

  will shut down the equipment.
•  For installation in wet locations,  

  protect the GFCI receptacle with a  

  weatherproof cover that will keep  

  both the receptacle and any plugs dry.
•  Must be installed in accordance with  

  national and local electrical codes.

CAUTION

!

Please read this leaflet  

completely before

getting started.

Receptacle

Outlet

Outlet

Mounting

Bracket

RESET 

button:

See step 8

TEST button:

See step 8
correct wiring/

trip

indicator

Cable  

Wires 

5.  Turn the power OFF

Cable  

Wires 

 

Next, plug in and turn ON the lamp or radio at 

the receptacle’s other outlet to make sure the 

power is OFF at both outlets. If the power is not 

OFF, stop work and call an electrician to  

complete the installation.

Placement in circuit:  

The GFCI’s place in the circuit determines if 

it protects other receptacles in the circuit.

Sample circuit:

Placing the GFCI in position A will also  

provide protection to “load side”  

receptacles B and C. On the other hand, 

placing the GFCI in position C will not provide 

protection to receptacles A or B. Remember 

that receptacles A, B, and C can be in  

different rooms.

C

Service

Panel

B

A

LOAD

LOAD

LINE

LINE

LINE

C

Service

Panel

B

A

LOAD

LOAD

LINE

LINE

LINE

TEST RESET

TEST

MONTHLY

SEE

INSTRUCTIONS

TEST RESET

TEST

MONTHLY

SEE

INSTRUCTIONS

TEST RESET

TEST

MONTHLY

SEE

INSTRUCTIONS

OLD

NEW (2)

BACK VIEW

FRONT VIEW

Grounding Terminal (Green):

Connection for bare

copper or green wire.

Screw (terminal) colors:

Green = grounding terminal

Silver  = white terminals

Brass   = hot terminals

LINE

Hot terminal (Brass):

Connection for the

LINE cable’s black 

wire.

LOAD

Hot terminal (Brass):

Connection for the

LOAD cable’s black 

wire.

A yellow sticker

covers the LOAD

terminals.  Do not

remove the sticker at 

this time.

LINE

White terminal (Silver):

Connection for the LINE

cable’s white wire.

LOAD

White terminal (Silver):

Connection for the  

LOAD cable’s white wire.

Installing and

Testing a GFCI

Receptacle

www.eaton.com

www.cooperwiringdevices.com 
EIS-0018-E (REV. B)

Отзывы: