Connecting the NET network
For more information visit:
www.EatonElectrical.com
MN05013005E
71
Connecting the NET
network
EZD with network connection (EZD-CP.-NT) can be used for
creating the NET network. Up to eight devices can be
connected to this network. Further information can be found in
the Chapter “EZ-NET Network, COM-LINK Serial
Accessories
Connection plug:
8-pole RJ45, EZ-NT-RJ45
Connection assignment of the RJ45 socket on the device
Figure 55: RJ45 socket
Connection cable:
chapter “Technical data”, Page 426
Figure 56: Connection assignment
ECAN_H data cable, pin 1, cable pair A
ECAN_L data cable, pin 2, cable pair A
Ground cable GND, pin 3, cable pair B
Select cable SEL_IN, pin 4, cable pair B
A
1 ECAN_H
A
2 ECAN_L
B
3 GND (Ground)
B
4 SEL_IN
1
2
3
4
5
6
7
8
J
Minimum operation with EZ-NET functions with the cables
ECAN_H, ECAN_L and GND. The SEL_IN cable is only
used for automatic addressing.