For more information visit:
www.EatonElectrical.com
EZ-NET Network, COM-LINK Serial
MN05013005E
348
Introduction to COM-LINK
The COM-LINK is a point-to-point connection using the serial
interface. This interface connection allows the reading of
input/output states as well as the reading and writing of
marker ranges. This data can be used for setpoint entry or for
display functions. The stations of the COM-LINK have
different functions. The active station controls the entire
interface connection. The remote station responds to the
requests of the active station. The remote station cannot
distinguish whether the COM-LINK is active or whether a PC
with EZSoft is using the interface.
J
Only the EZD can be the active station in a COM-LINK
connection.