7
Expertline LED Beacon Technical Manual
EXPERTLINE LED BEACON TECHNICAL MANUAL
TMF0056.A www.eaton.com
Schalterstellung / Switch-position /
/ Posición del
commutador
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Blitzlicht
Strobe light
Luz de destellos
Blinklicht
Blinking light
Luz intermitente
Rundumlicht
Rotating light
Luz omnidireccional
Dauerlicht
Continuous light
Luz continua
Position de commutation
Allumage de type flash
Allumage clignotant
Allumage fixe
Allumage rotatif
Terminal room
Wall mounting
Operating mode
User Information
This electrical equipment is an explosion-proof device designed for use in areas in which an explosive gas atmosphere
will probably occur from time to time during normal operation – as a group II category 2 device it is designed for use in
Zone 1. Thus the device is also suited for group II and category 3 applications and may be operated in Zone 2.
This device is also suited for operation in areas in which an explosive dust atmosphere will probably occur from time to
time during normal operation. As a group II and category 2 D device it may be used within Zone 21 and Zone 22.
Please note the following warnings and security information
1. The installation and adjustment of the device must be carried out by qualified personnel in accordance with the
prescribed installation regulations taking the specified type of protection into account.
2. The device should not be operated in areas in which strong charges are generated, machines work by friction or
cutting, electrons are sprayed (e.g. in the vicinity of electrostatic paint equipment), or pneumatically transported dust
occurs.
3. This apparatus is a Protective Class II device and may only be connected to and operated at the voltage it was
designed for. Please pay attention to the polarity information.
4. If the device is damaged, it may not be operated.
5. While operating the device in business or industry facilities, the legally required precautions against accidents resulting
from the use of electrical systems and devices must be taken.
6. The device may be operated solely under the stated ambient conditions. Unfavourable ambient conditions can lead to
damage of the device and thus present a potential danger for the user.
Such unfavourable ambient conditions could include:
•
moisture, dust (pay attention to the degree of protection)
•
Flammable gases, vapours, solvents not covered by the type of protection
•
too high ambient temperatures (>+65°C)
•
Too low ambient temperatures (<-40°C)
7. Repairs may be carried out by the manufacturer or by a person appointed by the manufacturer followed by a renewed
product conformity inspection.
Содержание Expertline
Страница 1: ...Expertline LED Beacon Technical Manual Eaton MEDC technical manual...
Страница 16: ...16 Expertline LED Beacon Technical Manual EXPERTLINE LED BEACON TECHNICAL MANUAL TMF0056 A www eaton com...
Страница 23: ...23 Expertline LED Beacon Technical Manual EXPERTLINE LED BEACON TECHNICAL MANUAL TMF0056 A www eaton com...
Страница 30: ...30 Expertline LED Beacon Technical Manual EXPERTLINE LED BEACON TECHNICAL MANUAL TMF0056 A www eaton com...
Страница 31: ...31 Expertline LED Beacon Technical Manual EXPERTLINE LED BEACON TECHNICAL MANUAL TMF0056 A www eaton com...