5 Application examples
5.3 Dual-channel controlled stop application (cat. 3, SIL 3, PL e)
42
EMS2…-SWD Electronic motor starter
10/19 MN120008EN
www.eaton.com
5.3 Dual-channel controlled stop application (cat. 3, SIL 3, PL e)
Figure 14:Dual-channel controlled stop application
The EMS2-D(R)OS-…-SWD motor starter is used in combination with an
ESR5-series safety relay.
A cable for the safety-oriented enable (EN+ / EN-) is connected via the safety
relay. For the enable, an external voltage of 24 V is used. This type of wiring
is then only accepted if the motor starter EMS2-…-SWD and the safety relay
are located in the same control panel.
SmartWire-DT
8
L1
L2
L3
0 V DC
24 V DC
F1
3/
L2
1/
L1
5/
L3
2/
T1
4/
T2
6/
T3
M
3 ~
S2
S2
S11 S12 S21 S22
+
- EN+ EN-
13
23
31
S33 S34
14
24
32
S3
W1
V1
U1
EMS2-D(R)OS-…-SWD