![Eaton EMR-5000 Скачать руководство пользователя страница 552](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919552.webp)
EMR-5000
IM02602012E
51P - Overcurrent Protection [51, 51C, 51V]
Available stages:
51P[1] ,51P[2] ,51P[3]
If you are using inrush blockings the tripping delay of the current protection functions must
be at least 30ms or more in order to prevent faulty trippings.
In order to ensure correct functioning of the directional detection after single-phase short-
circuits, the following reference voltage is used: For phase current
IA it is the line-to-line
voltage
VBC, for phase current IB the line-to-line voltage VCA and for phase current IC the
line-to-line voltage
VAB.
In case the fault happens to be near the measuring location and there is no reference
voltage for directional recognition available any more (neither measured or from history
(voltage memory)), then the module will - depending on the parameter setting - either trip
non-directional or it will be blocked.
All overcurrent protective elements are identically structured.
This module offers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
The following table shows the application options of the Overcurrent Protection element
Applications of the 51P-Protection Module
Setting in
Option
ANSI 51 – Short circuit protection, non-
directional
Device Planning menu
Criterion: Fundamental/TrueRMS
ANSI 51V – Voltage restraint overcurrent
protection
Parameter Set:
VRestraint = active
Criterion: Fundamental/TrueRMS
51C Voltage controlled overcurrent protection
(Please refer to the chapter
Parameter/Adaptive Parameter)
Adaptive Parameters
Criterion: Fundamental/TrueRMS
www.eaton.com
552
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...