EMR-5000
IM02602012E
Access Authorizations (access areas)
Passwords – Areas
The following table shows the access areas and the authorization passwords that they require in order to access them.
Area Symbol
Authorization Password
Access to:
Read Only-Lv0
Level 0 provides Read Only access to all
settings and parameters of the device. The
device will fall back into this level
automatically after a longer period or
inactivity
Prot-Lv1
This password provides access to the
reset- and acknowledge options. In
addition to that, it permits the execution of
manual trigger signals.
Prot-Lv2
This password provides access to the
reset and acknowledge options. In addition
to that it permits changing of protection
settings and the configuration of the trip
manager.
Control-Lv1
This password grants permission for
switching operations (switching
switchgears)
Control-Lv2
This password grants permission for
switching operations (switching
switchgears). In addition to that it gives
access to the switchgear settings
(switching authority, interlockings, general
settings of switchgears, Breaker wear...).
Supervisor-Lv3
This password grants non-restricted
access to all parameters and settings of
the device (device configuration). This
includes also the devices planning, device
parameters (e.g. Date and Time), Field
Parameters, Service Parameters and Logic
Parameters.
www.eaton.com
367
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...