EMR-4000
IM02602009E
Digital Inputs Output Signals on DI-8P X
Signal
Description
DI 1
Signal: Digital Input
DI 2
Signal: Digital Input
DI 3
Signal: Digital Input
DI 4
Signal: Digital Input
DI 5
Signal: Digital Input
DI 6
Signal: Digital Input
DI 7
Signal: Digital Input
DI 8
Signal: Digital Input
Wired Inputs (Aliases)
Available Elements:
Wired Inputs
The module
WiredInputs allows to alias Digital Inputs. By means of the menu [Device Para/WiredInputs] the user can
assign specific functions on digital inputs.
Alias Example: The 52a contact will be assigned/connected to Digital input1 (DI1). Once the 52a is aliased
(linked) on the DI1, the signal »WiredInput.52
A
« can be used instead of the DI1 signal for further processing
within the protective relay. That means, from now on any state changes of the Digital Input1 will we represented
by
the
»WiredInput.52
A
« signal.
www.eaton.com
79