46 - Current Unbalance Protection
Elements:
46[1] ,46[2]
This is the
46
device Current Unbalance setting, which works similar to the
47
device Voltage Unbalance setting. The
positive and negative sequence currents are calculated from the 3-phase currents. The Threshold setting defines a
minimum operating current magnitude of either I1 or I2 for the 46 function to operate, which ensures that the relay has a
solid basis for initiating a current unbalance trip. The »
%(I2/I1)«
setting is the unbalance trip pickup setting. It is
defined by the ratio of negative sequence current to positive sequence current »
%(I2/I1)«
for ABC rotation and »
%
(I1/I2)«
for ACB rotation. The device will automatically select the correct ratio based on the Phase Sequence setting in
the System Configuration group described above.
This function requires positive or negative sequence current magnitude above the threshold setting and the percentage
current unbalance above the »
%(I2/I1)« setting before allowing a current unbalance trip. Therefore, both the threshold
and percent settings must be met for the specified Delay time setting before the relay initiates a trip for current
unbalance.
All elements are identically structured.
www.eaton.com
576
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...