2.2.8.2
Common CT Wiring Configurations
Check the installation direction.
DANGER!
It is imperative that the secondary sides of measuring transformers be grounded.
DANGER!
The current measuring inputs may exclusively be connected to current measuring
transformers (with galvanic separation).
WARNING!
CT secondary circuits must always to be low-burdened or short-circuited during wiring /
installation work.
86
www.eaton.com
EMR-3MP0
2 Hardware
2.2 EMR-3MP0 – Installation and Wiring