IL05003010E.pdf 

                                   

5011630305-PA05

2007-05-08

 

ELC-PA10AADR 
ELC-PA10AADT 

Logic Controller with Built-in Analog 
Input/Output

 

Instruction Sheet

 

 

WARNING 

 

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, 
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and 
commands is compatible with ELC-PC/PA/PH series; please see ELC Application Manual. For more 
information about the optional peripherals , please see individual product manual. 

 

This is an OPEN TYPE Controller. The ELC should be kept in an enclosure away from airborne dust, humidity, 
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tools or 
keys to open the enclosure, so as to avoid the hazard to users and the damage to the ELC. 

 

Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the 
ELC. Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the ELC is 
properly grounded 

. Do NOT touch terminals when power on. 

 

Battery replacement: use UL component type: TDRTL-2150/S lithium battery. Refer to following table for 
battery life. (NOTE: RTC should be reset after changing battery). 

Temperature((

°

C) 

0  25 50 70 

Life 

(Years) 

9 8 6 5 

Precision of calendar timer: 

At 0

°

C/32

°

F, less than –117 seconds error per month. 

At 25

°

C/77

°

F, less than 52 seconds error per month. 

At 55

°

C/131

°

F, less than –132 seconds error per month. 

 

Warning – Do not disconnect while circuit is live unless area is known to be non-hazardous. 

 

Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - Article 
501-10(B)(1) of the National Electrical Code. 

 

Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only. 

 

Warning – Explosion hazard - Substitution of components may impair suitability for Class 1, Division 2. 

 

Warning – Explosion hazard - Do not disconnect equipment unless power has been switched off or the area is 
known to be Non-Hazardous. 

 

1  

INTRODUCTION 

1.1  Model Name Explanation and Peripherals 

Thank you for choosing Eaton Logic Controller (ELC) series products. The ELC-PA series is a 10-point (4DI+2DO+ 

2AI+2AO) controller unit. ELC-PA uses the same commands and functions as ELC-PA series, 2-CH 12-bit analog 

voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is also built-in, 2-digit 

7-segment display corresponds to internal register directly to display ELC station or user-defined code. 

1.2  Product Profile and Outline 

90

3

1

POWER

3

10

5

4

15

14

19

17

8

STOP

6

37.4

BAT.LOW

ERROR

RUN

RUN

7

1

9

2

3

12

11

18

16

ALARM

A

Y1

X1

RS

-4

85

RS

-2

32

13

D

X0

Y0

X3

X2

CH1

I

I

CH0

1+

0+

EL

C

-PA

10

AA

D

R

88

V1+

COM

s

D/A

I

I

CH1

0+

1+

V1+

V0+

V0+

A/D

s

C0

Y0

Y1

X3

X0

X1

X2

CH0

 

Unit: mm 

Warning: Battery replacement: Please change the battery within 3 

minutes, or the internal data of the ELC (including the program area, 

perpetual calendar and latched registers) could be lost or destroyed. 

1  Status indicator: POWER, RUN, 

ERROR, BAT.LOW, A

D, ALARM 

2 RUN/STOP switch 
3 2-digital 7-segment display 
4  Digital I/O terminal 
5  DIN rail clip 
6  Analog I/O terminals 
7  I/O point indicators 
8  COM1 (RS-232) (Rx) indicator 
9  COM2 (RS-485) (Tx) indicator 

10  COM1 (RS-232) programming port 

11 Nameplate 

12 Extension port 
13  Mounting hold of the extension unit 
14  DIN rail (35mm) 
15 Extension unit clip 

 

16 COM2 (RS-485) Communication 

port 

17 DC Power input 
18 2 pin removable terminal (standard 

accessory) 

19 Power input cable (standard 

accessory) 

20 Battery cover 
21 Battery socket connection 
22 Battery mount 

 

2  

FUNCTION SPECIFICATIONS 

 

Items 

Specifications 

Remarks 

Control Method 

Stored program, cyclic scan system 

 

I/O Processing Method 

Batch processing method (when END command is executed) I/O refresh command is available 

Execution Speed 

Basic commands (several us) 

Application Commands 
(10~hundreds us) 

Program Language 

Co Ladder Logic + SFC 

Including the Step commands 

Program Capacity 

7,920 STEPS 

SRAM + Battery 

Commands 

32 Basic sequential commands (including STL/RET) 

168 Application commands   

Re

la

y (b

it mo

de

X  External Input Relay 

X0~X177, octal number system, 128 points 

Total 256 

points 

Correspond to external I/O points 

Y  External Output Relay 

Y0~Y177, octal number system, 128 points 

Aux. 

Relay 

General 

M0~M511, 512 points (*1) 

Total 

4,096 

points 

Contacts can switch to On/Off in 
program 

Latched 

M512~M999, 488 points (*3) 
M2000~M4095, 2,096 points (*3) 

Special 

M1000~M1999, 1,000 points (some are latched) 

T Timer 

100ms 

T0~T199, 200 points (*1) 

Total 256 

points 

When the timer that set by TMR 
command reaches the preset 
value, the T contact with the same 
number will be On. 

T192~T199 for Subroutine 
T250~T255, 6 points Accumulative (*4) 

10ms 

T200~T239, 40 points (*2) 
T240~T245, 6 points Accumulative (*4) 

1ms 

T246~T249, 4 points Accumulative (*4) 

C Counter 

16-bit Count Up 

C0~C95, 96 points (*1) 

Total 250 

points 

When the counter that set by CNT 
(DCNT) command reaches the 
preset value, the C contact with 
the same number will be On. 

C96~C199, 104 points (*3) 

32-bit Count 
Up/Dn 

C200~C215, 16 points (*1) 
C216~C234, 19 points (*3) 

32bit High-speed 
Count Up/Dn 

C235~C242, 1 phase 1 input, 9 points (*3) 
C246~C249, 1 phase 2 inputs, 3 points (*3) 
C251~C254, 2 phase 2 inputs, 3 points (*3) 

Step 

point 

Initial Step Point  S0~S9, 10 points (*1) 

Total 

1,024 

points 

Usage device of step ladder 
diagram (SFC) 
Latched Range: 
Start: D1214 (K512) 
End: D1215 (K895)   

Zero Point Reset S10~S19, 10 points (use with IST command) (*1)
General 

S20~S511, 492 points (*1) 

Latched 

S512~S895, 384 points (*3) 

Alarm 

S896~S1023, 124 points (*3) 

Re

g

iste

r (WORD d

at

a

T  Current Value of the Timer  T0~T255, 256 points 

When the timer reaches the preset 
value, the contact of timer will be 
On. 

Current Value of the 
Counter 

C0~C199, 16-bit counter, 200 points 

When the counter reaches the 
preset value, the contact of 
counter will be On. 

C200~C254, 32-bit counter, 50 points 

Data 
Register 

General 

D0~D199, 200 points (*1) 

Total 

5,000 

points 

Can be memory area for storing 
data.    E and F can be used as the 
special purpose of index 
indication. 

Latched 

D200~D999, 800 points (*3) 
D2000~D4999, 3,000 points (*3) 

Special D1000~D1999, 

1,000 

points 

Index 

E0~E3, F0~F3, 8 points (*1) 

N

one

 

File Register 

0~1,599 (1,600 points) (*4) 

Extension register for storing data.

Poi

nt

er

 

For Master Control Nested 
Loop 

N0~N7, 8 points 

Control point of master control 
nested loop 

P  For CJ, CALL Commands  P0~P255, 256 points 

The location point of CJ, CALL. 

Inter

ru

pt

 

External Interrupt 

I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 (X4), I501 
(X5); 6 points (all are rising-edge trigger) 

The location pointer of interrupt 
subroutine 

Time Interrupt 

I6

□□

 (1ms), I7

□□

 (1ms), (

□□=

1~99ms) 

Hi-speed Counter   

I010, I020, I030, I040, I050, I060; 6 points 

Communication I150, 

point 

C

o

nst

ant

 

K Decimal 

K-32,768 ~ K32,767 (16-bit operation) 
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation) 

H  Hexadecimal 

H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation) 

Programming Port 

COM1: RS-232, COM2: RS-485 (Master/Slave), They can be used at the same time. 

Analog Volume / RTC 

ELC built-in bipolar 2-CH A/D, D/A, 12 bits, 2-digital 7-segment display, built-in RTC 

Special Extension Module 

Use the same modules of ELC series. (Max. 8 Extension Unit points) 

*1: The non-latched area is fixed, and can’t be changed.   

*2: The non-latched area can be changed to a latched area with parameter setting. 

*3: The latched area can be changed to a non-latched area with parameter setting. 

*4: The latched area is fixed, and can’t be changed. 

Auxiliary 

Relay 

General Latched 

Special 

auxiliary 

relay 

Latched 

M0~M511 M512~M999 

M1000~M1999 

M2000~M4095 

Non-latched (fixed) 

Latched (default) 

Some are latched and can’t be 

changed 

Latched (default) 

Start: D1200 (K512)   

End: D1201 (K999)   

Start: D1202 (K2,000)

End: D1203 (K4,095) 

Timer 

100 ms 

10 ms 

10ms 

1 ms 

100 ms 

T0 ~T199 

T200~T239 

T240~T245 

T246~T249 

T250~T255 

Non-latched (fixed) 

Non-latched (fixed) 

Accumulative Latched (fixed) 

Counter 

16-bit count up 

32-bit count up/down 

32-bit high-speed count up/down 

C0~C95 C96~C199 

C200~C215 

C216~C234 C235~C245 

C246~C255 

Non-latched 

(fixed) 

Latched (default) 

Non-latched 

(fixed) 

Latched (default) 

Latched (default) 

Start: D1208 (K96)   
End: D1209 (K199)   

Start: D1210 (K216)   

End: D1211 (K234)   

Start: D1212 (K235)   

End: D1213 (K255)   

Step relay 

For general 

Latched 

Special register 

Latched 

For general 

S0~S9 S10~S19

S20~S511 

S512~S895 

S896~S1023 

It is fixed to be non-latched 

Factory setting is latched 

It is fixed to be latched 

Start: D1214

K512

 

End: D1215

K895

 

Register 

General Latched 

Special 

registers 

Latched 

D0~D199 D200~D999 

D1000~D1999 

D2000~D4999 

Non-latched (fixed) 

Factory setting is latched. 

Some are latched and can’t 

be changed. 

Factory setting is 

latched. 

Start: D1216 (K200)   

End: D1217 (K999) 

Start: D1218 (K2,000) 

End: D1219 (K4,999) 

File Register 

K0~K1,599, Latched (fixed) 

When switching between power On/Off or ELC RUN/STOP modes: 

Memory Type 

POWER 

Off

Ö

On 

STOP

Ö

RUN 

RUN

Ö

STOP 

Clear all M1031 

non-latched area

Clear all 

M1032 latched 

area 

Factory 

Setting

Non-latched Clear 

Unchanged 

M1033=Off, clear 

Clear Unchanged 

M1033=On, unchanged 

Latched Unchanged 

Unchanged 

Clear 

Special M, Special D, 

Index register 

Initial 
value 

Unchanged Unchanged 

Initial 
value 

File register 

Unchanged 

 

3

BUILT-IN ANALOG I/O AND 7-SEGMENT DISPLAY 

 

Built-in 2-CH 12-bit A/D and 2-CH 12-bit D/A are bipolar. It can read A/D converted digital value and get designated 
analog output by reading special D or writing into special D. 

This built-in display corresponds to special D directly. User can use it to display error code or station when 
executing ELC LINK. It is great convenience for system maintenance. Refer following table for corresponding 
special D. 

Device No. 

Function 

Built-in Display 

2-digital
7-segment display

D1056 

Present value of AD channel 0 (CH0)   

D1057 

Present value of AD channel 1 (CH1)   

D1110 

Average value of AD channel 0 (CH0)   

D1111 

Average value of AD channel 1 (CH1)   

D1116 

DA channel 0 (CH0) 

D1117 

DA channel 1 (CH1) 

D1118 

Conversion sampling time (ms) 

 

Device No. 

Function 

M1196 

Number system setting for display (Off: Decimal, On: Hexadecimal) 

M1197 

The decimal point setting between the middle and the right-most numbers 

M1198 

The decimal point setting after the right-most number 

D1196 Display 

content 

 

4

ELECTRICAL SPECIFICATIONS 

 

               Model  
  Item 

ELC-PA10AADR/T 

Power supply voltage 

ELC: 24VDC (-15%~+20%) (With DC input reverse polarity protection),   
Extension Unit: supplied by the ELC 

Fuse 

2A / 250VAC 

Power Consumption 

5W MAX 

Insulation Resistance 

> 5 M

Ω

  at 500 VDC (Between all inputs / outputs and earth) 

Noise Immunity 

ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
RS: 26MHz~1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of terminals 24V and 0V 
(All ELC units should be grounded directly to the ground pole). 

Environment 

Operation: 0

~55

  (Temperature), 50~95% (Humidity), Pollution degree 2;   

D/A output operation: 0

~50

 (Temperature), 

Storage: -25

~70

 (Temperature), 5~95% (Humidity) 

Agency Approvals 

UL508 
UL1604, Class1,Div2    Operating temperature code: T5 
European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC 

Vibration / Shock Resistance 

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27 (TEST Ea) 

Weight (approx.) (g) 

158 

 

DC Input Point Electrical Specification 

Input Type 

DC (SINK or SOURCE) 

Input Current 

24VDC 5mA 

Active Level 

Off

On  

X0,X1: above18.5VDC 

On

Off 

X0~X3: below 8VDC 

X2,X3: above16.5VDC 

Responding Time 

About 10ms (An adjustment range of 0~20ms could be selected through D1020 and D1021) 

 

Output Point Electrical Specification 

Output Type 

Relay-R 

Transistor-T 

Current Specification 

1.5A/1 point (5A/COM) 

0.3A/1 point @ 40

; When the output of Y0 and Y1 is high-speed pulse, Y0 

and Y1 = 30mA 

Voltage Specification 

Below 250VAC, 30VDC 

30VDC 

Maximum Loading 

75VA (Inductive) 

9W/1 point 

When the output of Y0 and Y1 is high-speed pulse, Y0 and 
Y1 = 0.9W (Y0 = 32kHz, Y1 = 10kHz), Y0 can be 50KHz 
using D registers. 

90 W (Resistive) 