IL05003002E.pdf

 

                                   

5011629803-AN03

2007-05-08

 

ELC-AN04ANNN 

Analog to Digital Converter Module 

Instruction Sheet

 

 

WARNING 

 

This Instruction Sheet only provides descriptions for electrical specifications, general 
specifications, installation & wiring, troubleshooting and peripherals. For more information about 
the optional peripherals, please see ELC Application Manual. 

 

This is an OPEN TYPE Controller. The ELC should be kept in an enclosure away from airborne 
dust, humidity, electric shock risk and vibration. Also, it is equipped with protective methods 
such as some special tools or keys to open the enclosure, so as to avoid the hazard to users 
and the damage to the ELC. Do NOT touch terminals when power on. 

 

Never connect the AC main circuit power supply to any of the input/output terminals, as it will 
damage the ELC. Check all the wiring prior to power up. To avoid any electromagnetic noise, 
make sure the ELC is properly grounded 

 

Warning – Do not disconnect while circuit is live unless area is known to be non-hazardous. 

 

Power, input and output (I/O) wiring must be in accordance with Class 1, Div. 2 wiring methods - 
Article 501-10(B)(1) of the National Electrical Code. 

 

Suitable for use in Class 1, Division 2, Groups A, B, C, D or Non-Hazardous locations only. 

 

Warning – Explosion hazard - Substitution of components may impair suitability for Class 1, 
Division 2. 

 

Warning – Explosion Hazard - Do not disconnect equipment unless power has been switched 
off or the area is known to be Non-Hazardous. 

 

1  

INTRODUCTION 

1.1  Model Explanation and Peripherals

 

Thank you for choosing Eaton Logic Controller (ELC) series products. The analog input module 
receives external 4-point analog signal input (voltage or current) and transforms it into 14 bits digital 
signal. The analog input module of ELC-AN04ANNN can read/write the data of analog input module 
by using commands FROM / TO via ELC program.    There are 49 CR (Control Register) in each 
module and there are 16 bits in each register. 

1.2  Product Profile and Outline 

12

13

14

11

 

M

C
H
3

C
H
1

C
H
2

M

M

EXTENSION

PORT

1

3

2

3

5

6

8

7

4

8

9

10

60

90

ELC-A

N04A

NNN

3

C
H
4

M

25.2

3

 

Units: mm 

 

1. Status indicator (Power, RUN and ERROR) 

2. Model Name 

3. Extension unit clip 

4. Input/output terminal 

5. DIN rail clip 

6. Mounting hole of the extension unit 

7. Nameplate 8. Extension 

unit 

clip 

9. DIN rail (35mm) 

10. Extension port 

11. RS-485 Communication port 

12. 2 pin removable terminal (standard accessory)

13. DC power input 

14. Power input cable (standard accessory) 

 

1.3 External 

wiring 

Voltage Input
-10V ~ +10V

Current Input

-20mA ~ +20mA

V+

COM

Isolation Wire    1¡@

 

5

@

FG

I+

250

 Ω

~

~

V+

FG

I+

2

@

CH1

CH4

250

 Ω

24+

24-

3

@

AG

+15V

-15V

DC/DC

Converter

4

@

System 

Grounding

Class 3 Grounding

(100      or less)

 Ω

COM

CH1

CH4

104.7K

104.7K

 

AG

104.7K

104.7K

 

AG

Isolation Wire    1¡@

terminal of 

power module

Warning:

 DO NOT wire to the No function terminal. Use 

Copper Conductor Only, 60/75 °C.

 

Note 1:

 Please isolate analog input and 

other power wiring. 

Note 2:

 If connect to current signal, 

please short circuit between V+ and I+ 
terminals. 

Note 3:

 If noise is too loud, please 

connect FG to grounding. 

Note 4:

 Please connect 

 terminal 

of power module and 

 terminal of 

analog input module to system earth 
point and make system earth point be 
grounding or connects to machine 
cover.  

Note 5:

 If wave of input terminal of 

loaded is too big that noise interferes 
wiring, please connect capacitance with 
0.1~0.47uf 25V.

1.4  Terminal of analog module layout 

AN04ANNN 

AN02NANN 

AN04NANN 

AN06AANN 

PT04ANNN 

TC04ANNN 

EL

C

-AN

0

4

N

AN

N

COM

FG

COM

FG

V+

V+

I+

I+

COM

FG

COM

FG

V+

V+

I+

I+

 

EL

C

-AN

0

2N

AN

N

COM

FG

COM

FG

V+

V+

I+

I+

 

POWER

ERROR

D/A

COM

FG

I+

COM

FG
V+

COM

I+

V+

FG

V+

I+

COM

V+

FG

I+

E

L

C-

A

N

0

4NA

N

N

 

COM

COM

V+

V+

I+

I+

EL

C

-AN

06

AA

N

N

D

A

ER ROR

POWER

COM

I+

V+

COM

COM

V+

V+

I+

I+

COM

I+

V+

 

I-

L+

FG

L-

E

LC-

P

T

0

4A

N

NN

I-

L+

FG

L-

I-

L+

FG

L-

I-

L+

FG

L-

 

SLD

L+

L-

EL

C

-T

C

04

AN

N

N

SLD

L+

L-

SLD

L+

L-

SLD

L+

L-

 

 

2  

STANDARD SPECIFICATIONS 

2.1 Function Specifications 

FOUR CH. A/D MODULE 

VOLTAGE INPUT 

CURRENT INPUT 

Power supply voltage 

24 VDC(20.4VDC~28.8VDC) (-15

~+20%) 

Analog input channel 

4 channel / each module 

Analog input range 

±

10V 

±

20 mA 

Digital conversion range 

±

8,000 

±

4,000 

Resolution 

14 bits(1

LSB

=1.25 mV) 

13 bits (1

LSB

=5

μ

A) 

Input impedance 

200 K

Ω

 and above 

250

Ω

 

Overall accuracy 

±

0.5% of full scale at 25

(77

)  

±

1% of full scale during 0~55

 (32~131

Response time 

3 ms 

×

 channels 

Isolation method 

It has isolation between digital area and analog area. There is no isolation 
among channels.   

Isolation 

Field to Digital Area: 500V 
Field to Analog Area: 500V 
Analog area to Digital Area: 500V 
Field to 24VDC: 500V 

Absolute input range 

±

15 V 

±

32 mA 

Digital data format 

2’s complementary of 16-bit, 13 Significant Bits   

Average function 

Yes (CR#2~CR#5 can be set and setting range is K1~K100) 

Self diagnose function 

Upper and lower bound detection / channels 

Communication mode (RS-485) 

MODBUS ASCII/RTU Mode. Communication baud rate of 4,800 / 9,600 / 
19,200 / 38,400 / 57,600 / 115,200 bps. For ASCII mode, date format is 
7Bits, even, 1 stop bit (7,E,1). For RTU mode, date format is 8Bits, even, 1 
stop bit (8,E,1). The RS-485 is disabled when the ELC-AN04ANNN is 
connected in series to an ELC. 

Connect to ELC in series 

The input point of the first analog extension unit it connects from the near to 
the distant is from 0 to 7. The Max. is 8 modules and it won’t waste digital 
I/O point. 

Max. rated consuming power 

24 VDC(20.4VDC~28.8VDC) ( –15

%~

+20

), 2W, supply from external 

power 

Noise Immunity 

ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, 

Analog & Communication I/O: 1KV 

RS(IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m 

 

Grounding 

The diameter of the grounding wire cannot be smaller than that of terminals 

24V and 0V (if numerous ELCs are used at the same time, make sure that 

each ELC is grounded respectively to the ground poles)   

Vibration/Shock Immunity 

International Standard Regulations: IEC61131-2, IEC 68-2-6 (TEST Fc)/ 

IEC61131-2 & IEC 68-2-27 (TEST Ea) 

Operation/Storage Environment 

Operation: 0

~55

(temperature), 50~95% (humidity), pollution degree: 2; 

Storage: -25

~70

(temperature), 5~95% (humidity) 

Agency Approvals 

UL508 

UL1604, Class1,Div2  Operating temperature code: T5 

European community EMC Directive 89/336/EEC and Low Voltage 

Directive 73/23/EEC 

 

 

3

CR (CONTROL REGISTER) 

 

ELC-AN04ANNN 

EXPLANATION 

CR

No.

Comm. 

address

Latched Register 

name  b15 

b14 

b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#0 H 4000 O  R  Model type 

System used, data length is 8bits (b7~b0).   
ELC-AN04ANNN model code =H 88 

#1 H 4001 O  R/W  Input mode setting 

Reserved CH4 CH3 CH2 CH1 

Input mode setting: factory setting is H0000. 
Mode 0: input voltage mode (-10V~+10V). 
Mode 1: input voltage mode (-6V~+10V). 
Mode 2: input current mode (-12mA~+20mA) 
Mode 3: input current mode(-20mA~+20mA) 
Mode 4: Reserved. 

#2 H 4002 O  R/W  CH1 average number 

Average numbers setting of channel CH1~CH4. Setting range is K1~K100 
and factory setting is K10. 

#3 H 4003 O  R/W  CH2 average number 
#4 H 4004 O  R/W  CH3 average number 
#5 H 4005 O  R/W  CH4 average number 

#6 H 4006 X  R 

Average value of CH1 input 
signal  

Display average value of CH1~CH4 input signal 

#7 H 4007 X  R 

Average value of CH2 input 
signal  

#8 H 4008 X  R 

Average value of CH3 input 
signal 

#9 H 4009 X  R 

Average value of CH4 input 
signal 

#10 ~ #11 

Reserved 

#12 H 400C X  R 

Present value of CH1 input 
signal  

Display present value of CH1~CH4 input signal 

#14 H 400E X  R 

Present value of CH3 input 
signal 

Display present value of CH1~CH4 input signal 

#15 H 400F X  R 

Present value of CH4 input 
signal 

#16 ~ #17 

Reserved 

#18 H 4012 O  R/W 

To adjust OFFSET value of 
CH1 

Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB. 
Voltage input: setting range is K-4,000 ~K4,000 
Current input: setting range is K-4,000 ~K4,000 

#19 H 4013 O  R/W 

To adjust OFFSET value of 
CH2 

#20 H 4014 O  R/W 

To adjust OFFSET value of 
CH3 

#21 H 4015 O  R/W 

To adjust OFFSET value of 
CH4 

#22 ~ #23

 

Reserved 

#24 H 4018 O  R/W  To adjust GAIN value of CH1  GAIN setting of CH1~CH4. Factory setting is K4,000 and unit is LSB. 

Voltage input: setting range is K-3,200 ~K16,000. 
Current input: setting range is K-3,200 ~K10,400. 

#25 H 4019 O  R/W  To adjust GAIN value of CH2 
#26 H 401A O  R/W  To adjust GAIN value of CH3 
#27 H 401B O  R/W  To adjust GAIN value of CH4 

#28 ~ #29 

Reserved 

#30 H 401E X  R  Error status 

It is the data register to save all error status. Please refer to fault code chart 
for detail. 

#31 H 401F O  R/W 

Communication address 
setting 

Setting RS-485 communication address. Setting range is 01~255 and 
factory setting is K1 

#32 H 4020 O  R/W 

Communication baud rate 
setting 

It is used to set communication baud rate (4,800, 9,600, 19,200, 38,400, 
57,600, 115,200bps). Communication format: ASCII mode is 7Bit, even bit, 1 
stop bit (7,E,1). Communication format of RTU mode is 8Bit, even bit, 1 stop 
bit (8,E,1). 
b0: 4,800 bps (bit/sec).         b1: 9,600 bps (bit/sec). (factory setting) 
b2: 19,200 bps (bit/sec).        b3: 38,400 bps (bit/sec). 
b4: 57,600 bps (bit/sec).        b5: 115,200 bps (bit/sec). 
b6~b13: reserved.   
b14: exchange low and high byte of CRC check code (only for RTU mode) 
b15: ASCII / RTU mode selection 

#33 H 4021 O  R/W 

Reset to factory setting and set 
characteristics adjustable 
priority 

b15 b14 B13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

Reserved CH4  CH3  CH2  CH1 

Output latched setting, factory setting H0000 
Give CH1 setting for example:   
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, 

CR#24). When b0=1, inhibit user to adjust OFFSET and GAIN value of 
CH1 (CR#18, CR#24). 

2. b1 means if characteristic register is latched. b1=0 (factory setting, 

latched), b1=1 (not latched).   

3. When b2 is set to 1, all settings will reset to factory setting. 

 