EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 21 of 107
Some firmware may not be downgraded. Check with Eaton before downgrading the EC500 to an earlier
firmware version. This may not be possible, or downgrade with the wrong file may cause the EC500 to stop
operating, and require factory repair. Eaton may be able to supply a special downgrade file that will work
correctly.
It is likely that configuration settings will be lost if the firmware in the EC500 is downgraded. If a firmware
downgrade is required, trial the downgrade and check the configuration before implementing it at a site.
CONFIGURATION FILE
Configuration file for EC500 can be uploaded to Controller through Web Page.
➢
To Upload Configuration File
•
Obtain the appropriate Configuration File (EC500_nnn_GG.VV.RR.cnf) from Eaton.
•
Connect to the EC500 via a web browser (For details see Ethernet Communications on page
79).
•
Go to
System Config.
File Management.
Select
Config File Management.
•
Click on
Choose File
and select the Configuration File (EC500_nnn_GG.VV.RR.cnf).
•
Click on
Upload
and follow the prompts.
•
Web page & display will show progress.
•
Once full file has been uploaded successfully, EC500 will automatically reboot within 5
Seconds. User will need to login again.