EBMAFDD14-36  - ARC  FAULT  DETECTION  DEVICE  (AFDD)  DISTRIBUTION  BOARD

Instruction  leaflet LT1230 (01/21)

IMPORTANT NOTES

1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician i n   

a ccordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring Regulations 

BS7671), Construction (Design and Management) Regulations, HSG150 - Health and Safety i n Construction, Statutory requirements and 

a ny s pecific instruction issued by the Company.

2. After completing the installation and testing of this product it is essential that this l eaflet is drawn to the attention of the person 
res ponsible for its future operation and maintenance, and is at all times a vailable for ready reference.

3. These notes assume throughout  that the product is disconnected from the supply. It is essential that  this is done beforea ny work is 
ca rri ed out.
4. These Distribution Boards a re designed for use with Eaton AFDDs only. Failure to comply will result in i nvalid warranty a nd certification.

2.4Nm

300957 

EBMAFDD14  - 14  Way DB

300958 

EBMAFDD24  - 24  Way DB

300959 

EBMAFDD36  - 36  Way DB

Clip fit

This board is intended to be used 

with Eaton AFDD devices 

up to 40A

All unused ways must

Be covered with a 

blanking module, 

assembled and

fitted  in gangs of 3.

EMPB

Important:

Orientate  clip  next 

to busbar stack

Optional

SPD

position

Incoming        

Switch position

Before fitting the AFDD to the busbar ensure the terminals are 

fully open. Locate the AFDD square to the 

busbar and tighten the terminals.

General note: Tightening torque for 
M5 thread forming screws is 3.8Nm

Insert Lock into hole tighten back nut

Remove plastic knob

Fitting Optional  Door 
Lock EMDL & EMPL

SP MCB / RCBO

Fit SP device on live stab, 

ASLTT1001 direct 

connection  on neutral 

stab and EMBP blank in 

the spare module  space. 

ASLTT1001

SP Device

EMBP

Earth bolt 

15Nm

2.5Nm

Содержание EBMAFDD24

Страница 1: ...ply It is essential that this isdone beforeanyworkis carriedout 4 TheseDistributionBoardsare designed for use withEatonAFDDs only Failure tocomplywillresult ininvalidwarrantyan dcertification 2 4Nm 300957 EBMAFDD14 14 Way DB 300958 EBMAFDD24 24 Way DB 300959 EBMAFDD36 36 Way DB Clip fit This board is intended to be used with Eaton AFDD devices up to 40A All unused ways must Be covered with a blank...

Страница 2: ...t upstream ofthe incoming switch so secondary board switches independently ofthe primary board Neutrallink connection Remove knock out for N cable to exit When the neutral link kit is fitted then the cable is made up with a M6 lug and connected to the link terminal as shown The other end is connected to the incoming neutral terminal on the secondary board Make up 16mm tri rated cablewith Cembre AN...

Страница 3: ...Neutral cable to the SPD Tighten to 2 4Nm Connect the EARTH wire to the nearest common earth bolt Tighten to 15Nm Energise the System The Indicator should remain green Ifthe indicator turns RED de energise and contactthe Technical Services department 2 4Nm Separation Shield 300965 In some arrangements when thedistribution board is used in a cluster a 20mm spacer is required to allow thebottom and ...

Страница 4: ...n to follow the instructions given here and to ensure their continued availability in conjunction with the use of the product No responsibility can be accepted by us if these instructions are disregarded Further copies of these instructions and information concerning the installation and proper use of this product can be obtained by contacting the Technical Services Department Eaton Electric Limit...

Отзывы: