EBMAFDD14-36 - ARC FAULT DETECTION DEVICE (AFDD) DISTRIBUTION BOARD
Instruction leaflet LT1230 (01/21)
IMPORTANT NOTES
1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician i n
a ccordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring Regulations
BS7671), Construction (Design and Management) Regulations, HSG150 - Health and Safety i n Construction, Statutory requirements and
a ny s pecific instruction issued by the Company.
2. After completing the installation and testing of this product it is essential that this l eaflet is drawn to the attention of the person
res ponsible for its future operation and maintenance, and is at all times a vailable for ready reference.
3. These notes assume throughout that the product is disconnected from the supply. It is essential that this is done beforea ny work is
ca rri ed out.
4. These Distribution Boards a re designed for use with Eaton AFDDs only. Failure to comply will result in i nvalid warranty a nd certification.
2.4Nm
300957
–
EBMAFDD14 - 14 Way DB
300958
–
EBMAFDD24 - 24 Way DB
300959
–
EBMAFDD36 - 36 Way DB
Clip fit
This board is intended to be used
with Eaton AFDD devices
up to 40A
All unused ways must
Be covered with a
blanking module,
assembled and
fitted in gangs of 3.
EMPB
Important:
Orientate clip next
to busbar stack
Optional
SPD
position
Incoming
Switch position
Before fitting the AFDD to the busbar ensure the terminals are
fully open. Locate the AFDD square to the
busbar and tighten the terminals.
General note: Tightening torque for
M5 thread forming screws is 3.8Nm
Insert Lock into hole tighten back nut
Remove plastic knob
Fitting Optional Door
Lock EMDL & EMPL
SP MCB / RCBO
Fit SP device on live stab,
ASLTT1001 direct
connection on neutral
stab and EMBP blank in
the spare module space.
ASLTT1001
SP Device
EMBP
Earth bolt
15Nm
2.5Nm