Installation
62
02/16 MN05013001Z EN
Bus termination resistor
The physically first and last stations in the easyNET network
must each be terminated with a bus termination resistor.
• Value: 124
O
.
• Connection plug : EASY-NT-R.
Figure 23:
Bus terminating resistors
a
First station on the easyNet
b
Bus termination resistor
c
Last station on the EasyNET network
Physical location, place
Station number
1
1
2
3
2
I S1 - 14
1 2
1 2
1 2
1 2
QS 1 - 4
I S1 - 14
QS 1 - 4
3
AS-Interface
+ –
I S1 - 14
QS 1 - 4
8
I S1 - 14
QS 1 - 4
R 1 - 12
S 1 - 6
R 1 - 12
S 1 - 8
8
a
b
c
b