Displaying the status display of other stations
On each device with a configuration and a display with
operating buttons, you display the status of the inputs and
outputs of every other NET station.
X
For this change to the status display and press the ESC
button.
The cursor switches to the display of NET station NT1 and
flashes. The NET ID precedes the display of the input/output
ID (e.g. 1I..).
X
Change the number of the required NET station with the
Í
and
Ú
cursor buttons.
The input/output states of this NET station are shown in the
display (e.g. 3I../3Q..).
X
Press the ALT button several times if you wish to see the
locally set time, the date or the group fault alarms for
transistor outputs on this NET station.
Pressing the ESC button further will terminate the display of
the input and output states of this NET station and will
activate the local display of NET station NT1.
h
After the power supply s is switched on, the other NET
stations and NET stations of type easySafety start up NET
communication at different speeds. When these different
types are used on a NET in mixed operation and are
started simultaneously, a faster starting NET station will
set its diagnostics contact ID.. = 1 to indicate a NET
station of type easySafety as missing.
Solution: On all other NET stations delay the evaluation of
the diagnostics bit ID.. for the NET stations of type
easySafety by approx. 5 s by using the T function block
(timing relay).
1I12..........
NT1
MO 06:42
1Q1.......
RUN
3I12.....7....
NT3
MO 06:42
3Q1.3..6..
RUN
3R12.....7....
NT3
MO 06:45
3S1.3..6..
RUN