PT - Put value to the NET
293
02/16 MN05013001Z EN
PT - Put value to the NET
The PUT function block PT.. enables you to transfer a 32-bit
operand to the NET. This value can be transferred to the
standard circuit diagram.
The operand value is transferred and automatically read by
the corresponding GET function block GT of another NET
station.
easySafety allows the use of up to 16 PUT function blocks.
Function block
Figure 135: PUT function block
a
Coil PT..T_: Trigger coil, on a rising edge the function block
temporarily stores the input value and transfers it to the NET.
b
Input PT..I1: The value that is to be put onto the NET.
c
Contact PT..Q1: Closes while the trigger coil is active.
d
Contact PT..AC: Closes during the buffering of the input value
and its subsequent transfer to the network.
e
Contact PT..E1: Closes in the event of a transfer fault.
T_
PT...
PuT
a
b
c
d
e
Q1
>I1
AC
E1
DW