6. Function blocks
6.3 UF - User function block
A user-function-block-specific plausibility check will not be run when copying and past-
ing between user function blocks. All checks are identical to those run on the main pro-
gram.
Within the context of the plausibility check for a device, the system will check whether
the total number of user function blocks per device is less than or equal to 127. If the
plausibility check for a device outputs an error / warning for a user function block in the
"Report output" dialog box and the view for the user function block is not active or open
in the Programming view, double-clicking on the error / warning will activate, or, if
applicable, open the Programming view for the user function block and show exactly
where the error or warning is found.
Depending on the corresponding results, the following messages may appear after a
plausibility check:
l
FB input / FB output %2 is not part of the user function block's interface
l
The number for an FB input / FB output was not assigned without gaps
l
FB input %2 exceeds the maximum number of a total of 12 bit and analog inputs
l
FB output %2 exceeds the maximum number of a total of 12 bit and analog outputs
l
Operand %2 is not supported in user function blocks!
l
The number for operand %2 falls outside the permissible value range for user func-
tion blocks.
6.3.8 Importing a user function block
The import function makes it possible to load user function blocks (uf7 files) from a
folder. This function is available in the Programming view.
In order to be able to import user function blocks, all open user
function blocks must be unmodified.
If they are not, the following message will be output: If open
user function blocks are modified, an import will not be pos-
sible. Please save all modified user function blocks first..
Select a uf7 file and click on "Open"
The selected user function block will be added to the user function block management
group only if it meets certain criteria.
The following messages can occur:
l
User function block is already found in easySoft 7.
You do not need to import it. Do you want to select a different file?
l
A user function block with different content is already found in easySoft 7. Since it is
used in the project and the function block interfaces are different, the import is not
allowed. Do you want to select a different file?
easyE4
11/18 MN050009 EN www.eaton.com
449
Содержание easyE4 series
Страница 1: ...Manual 11 18 MN050009 EN easyE4 Manual...
Страница 4: ......
Страница 16: ...12 easyE4 11 18 MN050009 EN www eaton com...
Страница 22: ...0 1 About this manual 18 easyE4 11 18 MN050009 EN www eaton com...
Страница 40: ...1 easyE4 control relays description 1 10 Safety regulations 36 easyE4 11 18 MN050009 EN www eaton com...
Страница 169: ...easyE4 11 18 MN050009 EN www eaton com 165...
Страница 462: ...6 Function blocks 6 4 Timing and counter relay example 458 easyE4 11 18 MN050009 EN www eaton com...
Страница 490: ...7 System settings 7 16 Time and Date setting 486 easyE4 11 18 MN050009 EN www eaton com...
Страница 520: ...9 easyE4 inside 9 7 NET network 516 easyE4 11 18 MN050009 EN www eaton com...
Страница 524: ...10 Diagnostics messages of the operating system 10 2 Diagnostics buffer 520 easyE4 11 18 MN050009 EN www eaton com...
Страница 570: ...11 Connection to other devices 11 6 E mail function 566 easyE4 11 18 MN050009 EN www eaton com...
Страница 578: ...12 Faults 12 4 Functionality of the NET faulty 574 easyE4 11 18 MN050009 EN www eaton com...
Страница 582: ...13 Maintenance 13 3 Storage transport and disposal 578 easyE4 11 18 MN050009 EN www eaton com...
Страница 594: ...590 easyE4 11 18 MN050009 EN www eaton com...
Страница 614: ...610 easyE4 11 18 MN050009 EN www eaton com...