3 Commissioning
3.4 Status display
72
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
3.4 Status display
Status display
800
After power on, the easy800 shows the status display of the basic device.
The status display has four lines. If a local expansion is connected to easy800
standard, press OK to show the status display of the local expansion in the
display (
section “Status display additional information”, page 74).
Each dot of the status display represents the status of the corresponding
input, output, ID etc. If the operand number is indicated, the status is 1;
if a dot is indicated, the status is 0.
Figure 66:Status display when you switch on
Lines 1 and 4: Inputs/outputs
Line 1 shows the status of the basic device inputs. Line 4 shows the basic
device outputs and its operating mode (RUN, STOP or BUSY).
800 operating principle in the circuit diagram and function
Line 2: System information, diagnostics
You can change the content of line 2 (and 3) by pressing ALT. After the initial
power up, the easy800 device indicates with P- that the cursor buttons
(P buttons) are not active and therefore cannot be used as button inputs in
the standard circuit diagram. Active P buttons are indicated with P+
(
Section “P PUSHBUTTONS“, Page 303). The will show further system
information easy800in line 2 (
Section “Status display additional
information“, Page 74) depending on the parameters and the peripheral
devices connected.
Starting from the initial status display, you can press ALT twice to show the
following diagnostics messages in line 2 and 3:
LED orange flashing
Target configuration currently being determined
LED red flashing
One station too many
External device plug empty - station missing
Target configuration
≠
Actual configuration
LED red continuous light
No connection between easy800-SWD and the SWD line
Short-circuit of the 15 V DC device voltage
Inputs
1)
Weekday/Time
or Weekday/Date
Outputs
1)
RUN/STOP operating mode
1) On: I1, 2, 5 and Q3, 4
Off:...
I 12..5.......
P-
MO 11:50
Q ..34....
STOP
I 12..5.......
P-
MO 11:50
Q ..34.... STOP
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...