7 SmartWire-DT
7.1 Configurations
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
285
7.1 Configurations
The following different SWD configurations are possible:
1. Project configuration
Before easy800-SWD can be put into operation, the device must be
notified which SWD stations are present and how their parameters are
set. It must be clear which inputs and outputs of the SWD stations are
assigned to which operands in the circuit diagram. This information is
collected in the project configuration and stored with the program in
easy800-SWD. You create the project configuration using the
easySoft-Pro software.
2. Target configuration
Pressing the Config configuration button on the device determines the
actual configuration and stores it as the target configuration in
easy800-SWD.
3. Actual configuration
By this is meant the actual physical configuration present on the SWD
line. Every time easy800-SWD is started, the actual configuration is
determined and compared with the stored target configuration.
To operate the device, the target configuration and the project configuration
must be stored. Both must be identical. The device will only startup up error-
free if the actual configuration at the start matches the target and project
configuration.
Creating the project configuration
The easySoft-Pro software is required for the project configuration.
Information on this is provided in the Online Help of easySoft-Pro.
Changes to the program can then be made directly on the device without any
need of the software. This requires that display and operating elements are
connected to the easy800-SWD.
Change to the configuration
To change the configuration of the SWD line, such as by adding a new
station, you must change the project configuration and determine the target
con
fi
guration again. Proceed as described in
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...