5 Function blocks
5.4 BT, Data block Transformer
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
155
CPY mode, copy marker ranges
There is one source range and one destination range. The source range is
specified at >I1. The destination range is specified at >I2. The length of the
destination range is specified by the number of bytes at the >NO input.
The content of the source range is copied to the marker bytes in the
destination range.
The function block executes the copy operation if there is a rising edge from
1 to 1 at the BT..T_ (Trigger) coil.
The error outputs E1, E2 and E3 are evaluated regardless of the status of the
trigger.
Example 1:
Copy of marker blocks, direct definition of marker ranges
The value of marker byte 10 to 14 is to be transferred to marker bytes 20 to
24.
•
Parameters of function block BT01:
After a rising edge from 0 to 1 at coil BT01T_ the content of MB10 to MB14
is copied to the marker bytes MB20 to MB24.
•
Source range:
I1
MB10
•
Target range:
I2
MB20
•
Number of bytes:
NO
5
Source
range
Value of
source
marker range
(decimal)
Destination
range
Value of
destination
marker
range
(decimal)
MB10
42
MB20
42
MB11
27
MB21
27
MB12
179
MB22
179
MB13
205
MB23
205
MB14
253
MB24
253
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...