2.5.2 Connecting easy DC digital inputs
Use input terminals I1 to I12 , R1 to R12 to connect pushbutton actuators,
switches or 3 or 4-wire proximity switches. Given the high residual current,
do not use 2-wire proximity switches.
2.5.2.1 Connecting DC digital inputs on the basic unit
Figure 18:
Connecting easy-DC, easy-DA digital inputs
2.5.2.2 Connect digital DC inputs to the expansion unit
Figure 19:
Connecting EASY…-DC-E digital inputs
Table 4:
easy-DC input signals
L01
⫹
L01
⫺
0 V
l1
I2
I7
+...V
DC : +24 V
DA : +12 V
F1
Voltage range of the input signals
Input current
OFF signal
ON signal
easy500/
easy700
I1 to I6
0 - 5 V
15 - 28.8 V
3.3 mA at 24 V DC
I7, I8
≧
8 V DC
2.2 mA at 24 V
easy700
I9, I10
15 - 28.8 V
3.3 mA at 24 V DC
I11, I12
≧
8 V DC
2.2 mA at 24 V
easy600
R1 - R12
15 - 28.8 V
3.3 mA at 24 V DC
+24 V
0 V
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
E+ E-
R11 R12
0V
0V
+24V
Input 24 V
24 V
F1
Содержание easy500, easy700
Страница 1: ...Operating Instructions Control Relay 500 700 05 10 MN05013003Z EN replaces 05 04 AWB2528 1508GB...
Страница 4: ...II...
Страница 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 54: ...2 Installation 2 8 Connecting bus systems 50 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 190: ...5 settings 5 10 Displaying device information 186 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...
Страница 234: ...9 Glossary of terms 230 Operating instructions 05 10 MN05013003Z EN www eaton com...