Device operation
24
09/10 MN05013007Z-EN
DeviceNet setting the
slave address
Each DeviceNet slave requires a unique address (MAC ID) in
the DeviceNet structure. Within a DeviceNet structure, you
can assign a maximum of 64 addresses (0 to 63).
Each MAC ID must be unique within the entire bus structure.
There are three ways to set the DeviceNet address of an
EASY222-DN:
• Using the integrated display and keyboard on the easy
basic unit
• Using easySoft V3.01 or higher on the PC
• Using the configuration software of the installed master
PLC (possibly by means of an explicit message).
Setting the address at the basic unit with display:
Basic requirements:
• The respective basic devices (easy600, easy700, easy800
or MFD-Titan) and EASY222-DN are supplied with
voltage.
• The basic unit is accessible (password protection not acti-
vated).
• The basic unit has a valid operating system version.
• The basic unit is in STOP mode.
X
Press the DEL + ALT shortcut to change to the special
menu.
X
Use the cursor keys
Í
or
Ú
to change to the
CONFIGURATOR.
+
PASSWORD...
SYSTEM...
GB D F E I
CONFIGURATOR
PASSWORD...
SYSTEM...
GB D F E I
CONFIGURATOR