Control commands for easy700
140
09/10 MN05013007Z-EN
Example:
Data 1 (Byte 4) = 0x03
l
The values for the year time switch
of channels A and B appear in the parameter menu.
Table 71:
Index 01 – Control byte
Channel A, index 11/12
Index 0x11 channel A timepoint of switch on
Index 0x12 channel A timepoint of switch off
Data 1 (Byte 4) – day
Data 2 (Byte 5) – month
Data 3 (Byte 6) – year
Example:
The year time switch channel A is required to activate on
21.04.2004.
Index = 0x11
Data 1 = 0x15
Data 2 = 0x04
Data 3 = 0x04
The year time switch channel B is required to activate on
05.11.2012.
Index = 0x22
Data 1 = 0x05
Data 2 = 0x0B
Data 3 = 0x0C
Data 1
Bit 7
6
5
4
3
2
1
0
FB output
–
–
–
–
–
–
–
Q1
1)