Control commands for easy700
114
09/10 MN05013007Z-EN
Read marker: M1 – M16/N1 – N16
Unlike the write operation, the marker read operation reads
the entire marker area of a particular marker type (M or N) is
read.
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID: Read
88
–
0
Response:
Read successful
–
C2
Command
rejected
–
C0
1)
0
1
Len
01
01
1
2
Part no.
M marker
86
86
N Marker
87
87
2
3
Index
2)
00
00
3
4
Data 1 (Low Byte)
00
4
5
Data 2 (Low Byte)
00
5 – 6
6 – 7
Data 3 – 4
00
00
2) There are 16 M markers and 16 N markers.