Core Power Solutions (DV2-C16 Models)
20
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-71B July 2009
Step 3 - Connect cables
1
Connect the live (negative) cables to the live cable connection plates.
2
Connect the common (positive) cables to the system common bar.
Step 4 - Check terminations, secure cables and test insulation
1
Check all terminations are correct and tighten to 18.7 - 21.9Nm (166 -
194 inch-pounds).
2
Secure the cables with cable ties to ensure there will be no strain on the
terminals.
3
Test the insulation resistance of the cables.
Step 5 - Refit cabinet panels and push in the fuse fail detect circuit breaker
Procedure complete
DCB1000 10-Way circuit breaker distribution
"
Front cover (hinged, screw-fixed).
#
Circuit breaker cover
(polycarbonate).
$
Blank covers for unused circuit
breaker positions.
%
Up to 10 circuit breakers.
!
Live cable connection plates (shown
for vertical cable entry, horizontal
also available) 1-pole, 2-pole or 3-
pole to suit circuit breakers (3/8"
studs, 1" spacing).
&
Common bar, horizontal or vertical
mounting, holes suit 3/8" (M10)
bolts, 1" spacing.
Step 1 - Access circuit breakers
1
Open the hinged front cover.
2
Undo and remove the circuit breaker cover.
3
If necessary, remove cabinet side panels for rear/top access.
4
Switch off circuit breakers (if fitted).