Table 4. Troubleshooting
Problem
Possible Cause
Solution
UPS non-responsive (No LEDs or alarm)
UPS is powered off
Press ON/Off button for two (2) seconds.
Battery is Defective
Replace the battery.
UPS Fault
Contact Technical Support.
The UPS is always operating in Battery
Mode
Input may not be properly connected
Check the input connection
Input breaker is open
Before reconnecting equipment, verify
the load matches the UPS capability
specified and output has short circuit
protection. Contact Tech support.
Actual backup time cannot be achieved
Battery voltage is to low
Charge the battery at least 24 hours (8
hours = ~90%, 24 hours = 100%).
Overload
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
Battery defect
Replace the battery
UPS or charge failure
Contact Tech Support
Fault Code Displayed
Overload
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
UPS short-circuit
Contact Tech Support
UPS over-temperature
Remove unnecessary loads. Before
reconnecting equipment, verify the load
matches the UPS capability specified.
Make sure the UPS is installed in a pre-
tested area that is free of excessive dust
and has adequate airflow. Place the UPS
away from other units at least 8 in.
(20.32 cm) to avoid interference. For best
performance, keep the indoor
temperature between 32°F and 122°F (0°
C and 50°C).
UPS will not cold start
Powerlock
UPS must be initially connected to AC
power when upon unboxing. To
reactivate Powerlock, shut down the UPS
while AC mains is operating. Press the
power button continuously for 10 seconds
until you hear a BEEP from the buzzer,
then release the power button to set the
powerlock feature.
Содержание DIN500AC
Страница 1: ...p n 9340DC Revision A Advanced User Guide Eaton DIN Rail AC UPS DIN500AC DIN850AC ...
Страница 9: ...6 Eaton Din Rail UPS Advanced User Guide 9340DC Rev A UPS Dimensions ...
Страница 13: ...10 Eaton Din Rail UPS Advanced User Guide 9340DC Rev A AC Wiring ...
Страница 23: ...9340DCA 9340DC A ...
Страница 24: ...p n 9340DC Revision A Guia de Usuario Avanzado Sistemas UPS de CA para Riel DIN Modelos DIN500AC DIN850AC ...
Страница 32: ...6 SAI de riel DIN de Eaton Guia de Usuario Avanzado 9340DC Rev A Dimensiones del SAI ...
Страница 46: ...9340DCA 9340DC A ...
Страница 47: ...p n 9340DC Revision A Guide de l utilisateur avancé Onduleurs CA pour rail DIN Modèles DIN500AC DIN850AC ...
Страница 55: ...6 Onduleur sur rail DIN Eaton Guide de l utilisateur avancé 9340DC Rev A Dimensions de l ASI ...
Страница 59: ...10 Onduleur sur rail DIN Eaton Guide de l utilisateur avancé 9340DC Rev A Installation câblée de l onduleur ...
Страница 69: ...9340DCA 9340DC A ...