2.1 Electrical Checkout Instructions (For Use with Eaton Remote Alarm Panels)

WARNING:The following procedures should be carried out by a qualified electrician familiar with the electrical safety 
procedures associated with this product and its associated equipment.

2.2 Electric Remote Alarm Panels (Full Service) – For Electrical Schematic Refer to Figure #3

Note: The alarm buzzer can be silenced by pressing the 'Silence Alarm' button on the front of the controller.

2.2.    - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel

   - In the Fire Pump Controller press the 'Local Start' pushbutton, the controller will start
   - The 'Pump Running' LED should illuminate and the alarm will sound on the Alarm Panel
   - Press the 'Stop' pushbutton on the front of the fire pump controller

2.2.    - Move the disconnect handle on the Fire Pump Controller to the 'OFF' Position
          - The 'Common Alarm' and 'Phase Failure' LED's should illuminate and the alarm will sound on the Alarm Panel

   - Move the disconnect handle back to the 'ON' Position

2.2.3  - In the menu under the Alarm category, change the phase rotation to the opposite of what it is currently set for.
          - The 'Common Alarm' and 'Phase Reversal' LED's should illuminate and the alarm will sound on the Alarm    
            Panel

   - Return the menu setting to the correct rotation.

2.3 Diesel Remote Alarm Panels – For Electrical Schematic Refer to Figure #4

Note: The alarm buzzer can be silenced by pressing the 'Silence Alarm' button on the front of the controller.

2.3.1  - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel

   - Place the controller in the 'AUTO' mode by turning the Main Switch to “AUTO”
   - Start the controller by pushing the “Engine Test" button on the Diesel controller membrane / keypad, 

             then push the “Acknowledge” button.

   - The 'Engine Running' light should illuminate and the alarm will sound on the alarm panel
   - Place the controller in the 'OFF' mode by turning the Main Switch to “OFF”
   - The 'Not in Auto Mode' LED will illuminate and the alarm will sound on the alarm panel

2.3.2  - Place the controller in the 'AUTO' mode by turning the Main Switch to “AUTO”

   - 

 

   - Place a jumper between Terminal #38 & #11 in the Fire Pump Controller (Low Fuel)
   - The 'Common Alarm’ and ‘Low Fuel’ LED’s should illuminate and the alarm will sound on the alarm panel
   - Place the controller in the 'OFF' mode by turning the Main Switch to “OFF” 

Start the controller by pushing the “Engine Test" button on the Diesel controller membrane / keypad, 

             then push the “Acknowledge” button.

O & M Manual IM05805008K

Remote Alarm Panels

EATON DFDAP-M / FDAP-M

2

EATON Corporation www.chfire.com

Effective: March 2011

Содержание DFDAP-M

Страница 1: ...O M Manual IM05805008K Remote Alarm Panels EATON DFDAP M FDAP M Effective March 2011...

Страница 2: ...utton 3 2 4 2 Normal and Supervisory Backup Voltage 3 2 4 3 Audible Alarm 3 2 4 4 Silence Alarm Button 3 2 4 5 Normal Power ON LED 3 2 4 6 Output Contacts 3 2 4 7 Output Relays 3 2 4 8 Alarm Inputs 3...

Страница 3: ...cal codes and standards The controller should be located or so protected that they will not be damaged by water escaping from pumps or pump connections Current carrying parts of controllers shall be a...

Страница 4: ...minate and the alarm will sound on the Alarm Panel Return the menu setting to the correct rotation 2 3 Diesel Remote Alarm Panels For Electrical Schematic Refer to Figure 4 Note The alarm buzzer can b...

Страница 5: ...is pressed again or the alarm condition has been satisfied 2 4 5 Normal Power ON LED The normal power ON LED indicates when normal power is available and will turn off when the controller switches to...

Страница 6: ...IM05805008K Remote Alarm Panels EATON DFDAP M FDAP M N Y C APPROVED 15 49 393 11 56 294 9 55 243 4 74 120 8 00 203 9 75 248 n 0 27 n 7 x4 WALL MTG HOLES NOTE 1 ALL ENCLOSURES FINISHED IN FIRE PUMP RED...

Страница 7: ...l IM05805008K Remote Alarm Panels EATON DFDAP M FDAP M N Y C APPROVED 15 49 393 11 56 294 9 55 243 4 74 120 8 00 203 9 75 248 n 0 27 n 7 x4 WALL MTG HOLES NOTE 1 ALL ENCLOSURES FINISHED IN FIRE PUMP R...

Страница 8: ...Wiring Schematic Electric Remote Alarm Panel FDAP M FIGURE 3 6 EATON Corporation www chfire com O M Manual IM05805008K Remote Alarm Panels EATON DFDAP M FDAP M N Y C APPROVED Effective March 2011...

Страница 9: ...Wiring Schematic Diesel Remote Alarm Panel FDAP M FIGURE 4 7 EATON Corporation www chfire com O M Manual IM05805008K Remote Alarm Panels EATON DFDAP M FDAP M Effective March 2011 N Y C APPROVED...

Страница 10: ...treet NE Unit 124 Alberta Canada T Tel 1 403 717 2000 Fax 1 403 717 0567 email chcfirepump eaton com www chfire com Calgary 3N 0A4 2011 Eaton Corporation All Rights Reserved Printed in Canada Publicat...

Отзывы: