2.1 Electrical Checkout Instructions (For Use with Eaton Remote Alarm Panels)
WARNING:The following procedures should be carried out by a qualified electrician familiar with the electrical safety
procedures associated with this product and its associated equipment.
2.2 Electric Remote Alarm Panels (Full Service) – For Electrical Schematic Refer to Figure #3
Note: The alarm buzzer can be silenced by pressing the 'Silence Alarm' button on the front of the controller.
2.2. - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel
- In the Fire Pump Controller press the 'Local Start' pushbutton, the controller will start
- The 'Pump Running' LED should illuminate and the alarm will sound on the Alarm Panel
- Press the 'Stop' pushbutton on the front of the fire pump controller
2.2. - Move the disconnect handle on the Fire Pump Controller to the 'OFF' Position
- The 'Common Alarm' and 'Phase Failure' LED's should illuminate and the alarm will sound on the Alarm Panel
- Move the disconnect handle back to the 'ON' Position
2.2.3 - In the menu under the Alarm category, change the phase rotation to the opposite of what it is currently set for.
- The 'Common Alarm' and 'Phase Reversal' LED's should illuminate and the alarm will sound on the Alarm
Panel
- Return the menu setting to the correct rotation.
2.3 Diesel Remote Alarm Panels – For Electrical Schematic Refer to Figure #4
Note: The alarm buzzer can be silenced by pressing the 'Silence Alarm' button on the front of the controller.
2.3.1 - Turn power on to the Fire Pump Controller and to the Remote Alarm Panel
- Place the controller in the 'AUTO' mode by turning the Main Switch to “AUTO”
- Start the controller by pushing the “Engine Test" button on the Diesel controller membrane / keypad,
then push the “Acknowledge” button.
- The 'Engine Running' light should illuminate and the alarm will sound on the alarm panel
- Place the controller in the 'OFF' mode by turning the Main Switch to “OFF”
- The 'Not in Auto Mode' LED will illuminate and the alarm will sound on the alarm panel
2.3.2 - Place the controller in the 'AUTO' mode by turning the Main Switch to “AUTO”
-
- Place a jumper between Terminal #38 & #11 in the Fire Pump Controller (Low Fuel)
- The 'Common Alarm’ and ‘Low Fuel’ LED’s should illuminate and the alarm will sound on the alarm panel
- Place the controller in the 'OFF' mode by turning the Main Switch to “OFF”
Start the controller by pushing the “Engine Test" button on the Diesel controller membrane / keypad,
then push the “Acknowledge” button.
O & M Manual IM05805008K
Remote Alarm Panels
EATON DFDAP-M / FDAP-M
2
EATON Corporation www.chfire.com
Effective: March 2011