EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Disable/Enable Devices
This menu allows the customer to disable and enable selected detectors, zones or I/O’s.
Detectors and zones are self-explanatory, simply touch the Enabled/Disabled box against each zone
or device.
The disable I/O menu however, allows the user to disable FRE, FPE, AUX relay, Fault output and
panel Sounders 1 & 2.
When the panel is in Auto learn individual sounders CANNOT be disabled, the only method of
disabling sounders is by using the ‘Disable all outputs’ function, or, download text into the panel,
which will then allow the sounders to be disabled by zone or individually.
If a device is a
lready ‘in fire’ the system will not allow the user to disable it. The zone that the device
belongs in must be disabled; this function is still available if the panel is in fire.
If a complete zone is disabled, individual devices within that zone cannot be selected for re-enabling.
If the panel is part of a network, then devices can be disabled across the network by using the
‘Network disable/enable function’.
If a device or zone is disabled, then that disablement must be shown across all panels within the
network. (EN54 -13 and AS 1668)
Weekly Test
This function allows the user to perform a weekly test single-handed and will appear in the Log of
events as a test.
Once this function has been selected the panel starts a four-minute timer, when a call point is
activated within these four minutes the panel will operate the sounders and then silence and reset the
system.
On a later version (Display v3.3.53) the user is asked to do a manual reset, EN54 does not allow the
panel to automatically reset.
If no call point is activated within the four minutes the weekly test mode will be cancelled.
During this test mode the relay outputs controlling plant and equipment shutdown will not
operate, neither will the FRE nor FPE outputs.
FRE: Fire Routing Equipment typically used to operate a remote centre communicator.
FPE: Fire protecting Equipment typically used to control fire doors.
Note: If ‘disable all outputs’ is selected, weekly test or walk test will still make the sounders operate
See Also High-Level Menu, page 41 (Global Weekly and Walk Tests)
Check Auto Config
This function has two purposes, the first is to check that when a database has been downloaded the
transmitted data matches the device data on the loop and then it highlights any anomalies as device
unknown or device type mismatches. It will also highlight any un-addressed (254) devices. Stating a
‘New Device’ (V1.50 2004)
The second is to pinpoint any o/c or s/c faults on the loop. The panel achieves this by electronically
disconnecting the return legs and interrogates the devices from the start of the loop. If there is a
break the panel will go to fault stating the first device it cannot see beyond the break. This same
function also pinpoints short circuits in the same way, creating a fault beyond the point where an
isolator has opened.
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...