EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Loading and Totals
The general rules are that the panel is capable of supporting up to 200 devices per loop; this can be a
combination of Detection, Callpoints, I/O units, Repeaters and Sounders.
The protocol and internal memory are constructed in such a way that there are certain loading rules
which must be strictly enforced.
Maximum 200 devices per loop
Maximum 60 sounders/beacons/sounder beacons (set low) per loop.
Maximum 20 I/O units per loop which assumes each I/O uses 3 output channels;
Maximum 120 Output channels based on 2 + 3 above.
Certain devices have been constructed to circumvent these rules effectively ‘fooling’ the panel to
offset some of the totals. The maximum 200 per loop CAN NOT be changed.
The totals for EN and UL are the same unless specified in the remarks column.
Device Type
Total per
Loop
Replies as
Remarks
Detectors
200
Optical, Heat or Opto Heat
Call points
200
Callpoint
Sounder/Beacon/Sounder
beacon
60
Sounder Beacon
Individuals all reply the same
MIO/ULCIO (single and 3 chan)
20
3 Chan I/O
MIO324S resets on silence
MCOM/ULMCOM
20
3 Chan I/O
MCOMS/ULMCOMS
60
Sounder Beacon
Uses 1 sounder channel,
ULMCOMS resets on silence
MCOM-FC
60(48)
Sounder/Beacon
Does not respond to EVAC
MCOM - R
20
3 Chan I/O
Not used for UL
MCIM (old version)/ULMCIM
20
3 Chan I/O
MCIM obsolete
MCIM-C/ULMCIM-C
200
Callpoint
MCIM-C obsolete
MCIM - NF
200
Non
– Fire input
Obsolete
MCIM (new version)
200
Input
Not used for UL
Spur Isolator
200
Takes no address
– does
take a load.
EN / UL Zone/Shop unit
Monitors (incl. Mini Module)
20
ZMU/SMU
(Acts as an output device)
Loop loader allows 20
conventional detectors
4 Way Sounder controller
20
SCU
Uses I/O channels
Repeater/Mimic/CIOP/BS7273
Device
200
Repeater
Restricted by load (20) Note
1
Beam Detector
200
Beam Detector
Restricted by load (20) Note
1
4
– 20 mA
20
4
– 20mA
Fan Controller
48 Chan’s Fan Controller
2xFC6
Tech I/O unit
20
I/O and Tech Input
Item takes 2 addresses
Addressable Remote Indicator
60
Sounder Beacon
Gas Interface
N/A
Discontinued
For Australia market
Table 1
Note 1
– The figure in brackets is a recommended total for these devices, there is currently no
restriction placed in the Loop loader program.
Note 2
–
Where total per loop is shown this is a maximum number or a maximum combination with
other output device
Содержание DF6200
Страница 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Страница 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Страница 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Страница 84: ...84 Amended Sept 21 Fig 79...
Страница 94: ...94 Amended Sept 21 Return to beginning of document End of Document...