3 Installation
3.5 EMC installation
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
61
3.5.5 EMC cable brackets
Frame-size-specific DX-EMC-MNT-… cable brackets can be used to easily
route and secure cables in the connection area of a DC1-S… variable
frequency drive with a frame size of FS1 or FS2 and an IP20 degree of
protection. These cable brackets are mounted on the variable frequency
drive’s mains connection side (DX-EMC-MNT-…
N
) and motor side
(DX-EMC-MNT-…
M
) using the corresponding mounting holes, and are then
connected to the drive’s earthing
.
The cable brackets’ integrated hole pattern (M4 screw tread) makes it
possible to secure the cables being connected and relieve any strain on them
by using the corresponding gland plates. It also makes it possible to have a
good 360° EMC connection (PES) in the case of screened cables.
These cable brackets are made of galvanized sheet steel.
Table 5:
Cable brackets
Figure 35: DX-EMC-MNT-...
N
(left), net and
DX-EMC-MNT-...
M
(right), motor, cable brackets
Cable bracket
Size DC1-S… in
IP20
gland plates
Quantity
designation
DX-EMC-MNT-1N
FS1
1
Mains connection
DX-EMC-MNT-1M
FS1
2
Control cables, motor connection
DX-EMC-MNT-2N
FS2
1
Mains connection
DX-EMC-MNT-2M
FS2
3
Control cables, motor connection,
external braking resistance
→
We recommend connecting the DX-EMC-MNT-… cable
brackets to the variable frequency drive before installing it.
→
For more information and technical data on DX-EMC-MNT-…
EMC cable brackets, please refer to instruction leaflet
IL040010ZU.