04
/18
IL
04020
012Z
8/12
Emergency On Call Service: Local representative
Eaton.eu/aftersales
or +49 (0) 180 5 223822 (de, en)
USA: EatonCare at
Eaton.com/eatoncare
or 877-386-2273
→
P1-13 = 11
P1-12 = 0
Input
L: 0 - 4 V DC
H: 8 - 30 V DC
Output
External 24 V DC (100 mA)
1
+24 V DC, < 100 mA
Digital Input 1 (DI1)
Stop
Enable,
Run Forward Rotation
2
Digital Input 2 (DI2)
Stop
Enable,
Run Reverse Rotation
3
Digital Input 3 (DI3)
AI1
FF1/FF2
4
5
+10 V DC, < 10 mA
Analog Input 1 (AI1): 0 - 10 V DC, < 20 mA, Frequency Setpoint value
[Digital Input 4 (DI4)] → P1-13
6
0 V
7
0 V
8
Analog Output 1 (AO1): 0 - 10 V DC, < 20 mA, Output Frequency
[Digital Output 1 (DO1)] → P2-11, P2-12
0 V
9
0 V
Digital Input 5 (DI5)
[Analog Input 2 (AI2)]
→ P1-13
FF1, Fixed Frequency
(P2-01 = 5 Hz)
FF2, Fixed Frequency
(P2-02 = 10 Hz)
10
11
Analog Output 2 (AO2): 0 - 10 V DC, < 20 mA, Output Current
[Digital Output 2 (DO2)] → P2-13, P2-14
Safe Tourqe Off
Stop
STO+ (18 - 30 V DC)
12
Safe Tourqe Off
Stop
STO- (0 V)
13
14
Relay (K11 = COM)
15
Relay (K14 = NO), Healthy
16
Relay (K12 = NC), Error
17
Relay (K23 = COM)
18
Relay (K24 = NO), RUN
Thermistor
Thermistor
Thermistance
Termistor
Termistore
热
热敏
敏电阻
电阻
Термистор
Thermistor
Thermistor
Θερμίστορ
Thermistance
Termistor
Termistori
Termistor
Termistor
Termisztor
Termistors
Termistorius
Termistor
Termistor
Termistor
Термистор
Termistor
Termistor
K1
K2
en
de
fr
es
it
zh
ru
nl
da
el
pt
sv
fi
cs
et
hu
lv
lt
pl
sl
sk
bg
ro
hr
T1 T2
M 3 ∼
Thermoclick sensor
ϑ
ϑ
U
V
W PE
PTC type, 2.5 kΩ trip level
PES
1 2 3 4 5 6 7 8 9 10 11 12 13
+
P-
+
P-
Error: External Fault
P1 - 13 = 6
P1 - 13 = 7
P1 - 13 = 16
P1 - 13 = 17
P2 - 33 =
Ptc-th
→
→
→
E-triP