background image

IL01906001E

For more information visit: www.EatonElectrical.com

Arcflash Reduction Maintenance 

Switch™ Application and Installation

Instructional Literature

New Information

Description

Page

1. Arcflash Reduction Maintenance Switch 

Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

2

2. Arcflash Reduction Maintenance Switch Installation

Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5

3. Installing the Arcflash Reduction Maintenance Switch 

in a DS Retrofitted Breaker . . . . . . . . . . . . . . . . . . . . . 

6

4. Installing the Arcflash Reduction Maintenance Switch 

in a Non-DS Retrofitted Breaker  . . . . . . . . . . . . . . . . . 

7

5. Completion of the Arcflash Reduction Maintenance 

Switch Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . 

8

6. Setting and Testing the RSM  . . . . . . . . . . . . . . . . . . . 

14

7. The Arcflash Reduction Maintenance Switch Installation 

Components for DS and Non-DS Breakers  . . . . . . . . . . 

15

Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

16

Appendix B  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

18

SAFETY PRECAUTIONS

Periodic testing of this devise is required (see  Section 6 “Set-

ting and Testing the RSM”).

Only qualified persons, as defined in the National Electric Code, 

who are familiar with the installation and maintenance of power 

circuit breakers and their associated switchgear assemblies 

should perform any work associated with these breakers.

Completely read and understand all instructions before attempt-

ing any installation, operation, maintenance, or modification of 

these breakers.

Always turn off and lock out the power source feeding the 

breaker prior to attempting any installation, maintenance, or 

modification of the breaker.  Do not use the circuit breaker as 

the sole means for isolating a high voltage circuit. Follow all 

lockout and tagging rules of the National Electric Code and all 

other applicable codes, regulations, and work rules.

Do not work on a closed breaker or a breaker with the closing 

springs charged.  Trip (open) the breaker and be sure the stored 

energy springs are discharged before performing any work.  The 

breaker may trip open or the charging springs may discharge, 

causing crushing or cutting injuries.

For drawout breakers, trip (open), and then remove the breaker 

to a well-lit work area before beginning work.

Do not perform any maintenance: including breaker charging, 

closing, tripping, or any other function which could cause sig-

nificant movement of the breaker while it is on the extension 

rails.  Doing so may cause the breaker to slip from the rails and 

fall, potentially causing severe personal injury to those in the 

vicinity.

Do not leave the breaker in an intermediate position in the 

switchgear cell.  Always leave it in the connected, discon-

nected, or (optional) test position.  Failure to do so could lead 

to improper positioning of the breaker and flashover, causing 

death, serious personal injury, and / or property damage.

Do not defeat any safety interlock.  Such interlocks are 

intended to protect personnel and equipment from damage due 

to flashover and exposed contacts.  Defeating an interlock 

could lead to death, severe personal injury, and / or property 

damage.

WARNING

POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, 

HIGH ENERGY OPERATING MECHANISMS.  THE BREAKERS AND 

THEIR ENCLOSURES ARE SIGNED WITH SEVERAL BUILT-IN INTER-

LOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND 

PROPER OPERATING SEQUENCES.  TO PROVIDE MAXIMUM PRO-

TECTION FOR PERSONNEL ASSOCIATED WITH THE INSTALLATION, 

OPERATION, AND MAINTENANCE OF THESE BREAKERS, THE FOL-

LOWING PRACTICES MUST BE FOLLOWED.  FAILURE TO FOLLOW 

THESE PRACTICES MAY RESULT IN DEATH, PERSONAL INJURY, OR 

PROPERTY DAMAGE.

BCS Switchgear Inc.

Switchgear | Circuit Breakers | Parts | Tech Support

bcsswitchgear.com | 888.599.0486

Need Help? 888.599.0486

Содержание CUTTLER-HAMMER Arcflash Reduction Maintenance...

Страница 1: ...th the closing springs charged Trip open the breaker and be sure the stored energy springs are discharged before performing any work The breaker may trip open or the charging springs may discharge cau...

Страница 2: ...t currents that flow through the circuit breaker associated with the Arcflash Reduction Mainte nance Switch This setting choice normally does not change unless there are future system modifications th...

Страница 3: ...12 16 kA 10 pickup range of 10 94 to 13 38 kA 3 Setting 5 9 1600 A 9 44 kA 10 pickup range of 8 50 to 10 38 kA 4 Setting 4 0 1600 A 6 40 kA 10 pickup range of 5 76 to 7 04 kA 5 Setting 2 5 1600 A 4 00...

Страница 4: ...T 7 SDPU 6 9600A SDT 0 2 I 2 T Out Manufacturer CUTLER HAMMER Description Digitrip RMS 510 910 Frame Model 1600 A Sensor Trip 1600 0 A Plug 1600 0 A Settings Phase LDPU 1 1600A LDT 7 SDPU 6 9600A SDT...

Страница 5: ...it Kit A Trip the breaker and remove it from the cell Move the breaker to a clean well lit work area Note It is the responsibility of the installer to insure that the breaker and all original componen...

Страница 6: ...efore 06 05 P N 256P726H04 follow the procedures detailed in Appendix A to install an updated DS Interface Board See Fig ure 5 to help identify which DS Interface Board is installed in the breaker Fig...

Страница 7: ...nance Switch Components Installed on a Non DS Breaker Note The Arcflash Reduction Maintenance Switch can be installed on any Retrofitted breaker using an Eaton 10 series Digitrip trip unit 510 610 810...

Страница 8: ...er Each installation of the Arcflash Reduction Maintenance Switch mode selector switch indicator light and battery holder may vary due to the type of breaker type of cell or components options mounted...

Страница 9: ...that the harness connecting the mode selector switch to the indicator light is short so the indicator light must be installed in close proximity to the mode selector switch Mark the center of the moun...

Страница 10: ...rface D Using the battery holder as a template mark then drill four 4 0 109 holes in the mounting surface to accept the battery holder mounting screws Figure 17 Marking the Battery Holder Mounting Hol...

Страница 11: ...y with the indicator light housing The con tact block assembly is self locking Insert the contact block assembly into the indicator light until the locking click is heard Ensure it is locked into plac...

Страница 12: ...on to the RSM making sure it is away from any moving parts within the breaker In routing the harness be sure to leave a service loop in the harness to facilitate racking the breaker in to and out of t...

Страница 13: ...ce and away from any moving parts within the breaker F For more information on the RSM wiring and additional cus tomer connections refer to the wiring and connections draw ing Figure 29 G Disconnect t...

Страница 14: ...evice clear all newly installed components and harnesses Step 4 Activating the RSM A To activate the RSM turn the mode selector switch to the Maintenance Mode position Close the LOTO cover then follow...

Страница 15: ...variety of breakers with which the Arcflash Reduction Maintenance Switch Installation can be used some excess hardware may remain when the Arcflash Reduction Maintenance Switch Retrofit is complete SE...

Страница 16: ...the 2 112 40 0 25 thread cutting pan head screws supplied B Note the connection point of each harness to the DS Interface Board positions P1 through P10 Mark each harness for reconnection later in th...

Страница 17: ...it Mounting Frame Figure 34 New DS Interface Board Installed on the Trip Unit Mounting Frame G Using the remaining screws spacers and lock nuts removed in Step D or the supplied 112 40 hardware secure...

Страница 18: ...erature Page 18 Effective May 2005 Arcflash Reduction Maintenance Switch Application and Installation Appendix B Sample Text Data Sheet SETTING MULT PICKUP R1 9 8 X R2 7 6 X R3 5 9 X R4 4 0 X R5 2 5 X...

Страница 19: ...IL01906001E For more information visit www EatonElectrical com Instructional Literature Effective May 2005 Page 19 Arcflash Reduction Maintenance Switch Application and Installation Notes...

Страница 20: ...d to be all inclusive or cover ing all contingencies If further information is required Eaton should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR P...

Отзывы: