Power Supply and Ports
Connect DC Power
Your PanelMate ePro unit is designed to operate at
24VDC -15%/+20%. A removable three-position
DC power connector attaches to the unit's
connector receptacle. The DC input common
(-terminal) and the chassis GND terminal are both
internally connected to the PanelMate ePro
chassis.
Note:
Use #18 AWG (0.82mm2) copper wire for
power and ground lead connections.
Note:
Power conditioning may be required when
the PanelMate ePro unit is installed in areas of poor
power quality.
Note:
Cutler-Hammer power supply: Catalog
Number 1219B is available for converting
120/230VAC to 24VDC.
CAUTION
Your PanelMate ePro unit could be severely
damaged if it is connected to voltages outside
the range of 18 to 30VDC. While your PanelMate
ePro unit is fully protected against polarity
reversal, damage can occur if the unit is not
wired correctly.
+
-
GND
+
-
GND
CAUTION
If you are converting from a PanelMate powered
from a 24VDC power supply be sure to check
the rating of your existing 24VDC power supply.
The PanelMate ePro unit requires a power
supply rated for 1.6A operation.
DB9, RS232 Serial Port (COM2)
DB9, RS232 Serial Port (COM1)
Standard VGA Video Output
10/100 Fast Ethernet RJ45 Port
PS/2 Mouse
PS/2 Keyboard
USB Port for M-Systems
DiskonKey
®
or Iomega Devices