2
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
•
6U height that fits any standard 19-inch rack (see Figure 2)
•
Normal operating mode that minimizes heat generation by operating typically at >98% efficiency. The UPS
filters incoming AC power and provides consistent power to your equipment without draining the battery.
•
For utility line input that exceeds normal operating range, automatic transfer to an online, double-
conversion, high-frequency UPS design with pure sine wave output and power-factor correction.
•
ABM
®
technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life.
•
Hot-swappable electronics module and batteries that simplify maintenance by allowing you to replace
them safely without powering down the critical load.
•
Emergency shutdown control through the remote emergency power-off (REPO) port.
•
One standard communication option with a DB-9 serial port and two open communication bays (X-Slot)
that allow a number of communication options.
•
Firmware that is service upgradable through the DB-9 communication port.
Figure 2. Standard Cabinet Used for BladeUPS
Содержание BladeUPS none
Страница 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Страница 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Страница 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Страница 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Страница 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Страница 160: ...16420164914 164201649 14 ...