0359-CPR-00419

2. Connection details

1a. Mounting base (IP21C)

1b. Mounting base (IP66C)

Table 1. Specification

Technical data

Effective September 2014

FXN009SB/EF009SB

FXN009SBWP/EF009SBWP

FXN009/EF009

FXN009WP/EF009WP

Wall sounder/beacon
Wall sounder

Supply voltage (BiWire alarm)  25.5~35 Vdc

Supply voltage 

(BiWire standby)

  18~25.5 Vdc

Supply voltage 

(conventional)

   18~35 Vdc

Cable size/type 

 

 0.5~2.5mm/FIRETUF, FP200 

    

or 

MICC

Standby current 

(BiWire mode)

   <15μA

Current (high volume) 

 Sdr only = 4.7mA, AV = 11mA

Current (low volume) 

 Sdr only = 2.6mA, AV = 8.7mA

Sound output (high volume)    99 +/- 3dB(A) : All tones

Sound output (low volume)    89 +/- 3dB(A) : All tones  

Operating temperature 

  -25 to +70ºC (93% ± 3%RH)

Material   

 

  ABS FR plastic

Environmental category 

  Type A= IP21C/ Type B= IP66

Tones 

 

 

  3, See section 3

Flash rate  

 

  0.5Hz (

N/A to FXN009(WP), EF009(WP)

)

Flash on period 

 

  60ms (

N/A to FXN009(WP), EF009(WP)

)

Feature

Value

Feature

Value

BiWire Ultra range:

Wall sounder/beacon IP66
Wall sounder IP66

 50 

 50 

 60 

(i) Drill required holes for

    cable gland fixing.

(iii) Fix to mounting surface

     using two suitable screws.

(ii) Drill out the required 

     fixing holes.

Drill position for rear 

cable entry

Drill position for 

glands

 50 (IP33) 

 50 (IP33) 

 75 (IP66) 

 97 (IP66) 

 62 (IP33) 

(i) Drill required holes for cable gland fixing (top or bottom) 

    and ensure cables are correctly sealed for IP66 integrity.

(ii) Fix to mounting surface using four suitable screws.

Drill position 

for glands

Use these four holes 

to ensure IP66 integrity

1

2

3

4

5

1

On

Off

3. Switch position meaning

1, Sounder on/off (AV version only)

2, Volume high (Off)/low (On)

3, Tones

4, Tones

5, Mode: On = BiWire, Off = Conventional

Continuous: 3=On, 4=On (984Hz)

Bell: 3=On, 4=Off  (1440Hz)

Alternating: 3=Off, 4=On (644/984Hz)

{

OUT

IN

SCREEN

ZONE OUT

ZONE IN

+VE  -VE

+VE  -VE

ZONE IN

ZONE OUT

Screen must be continuous along entire length of loop.

Compliance EN54-3; EN54-23:2010

14

(Conventional compatible)

25-12766-E

2

  Note

  All products meet minimum requirements of IP33C in 

  accordance with EN54-3.

www.acornfiresecurity.com

www.acornfiresecurity.com