background image

18

Instruction Book    

IB182221EN   September 2017   www.eaton.com

GE AM [Cable or Hard Bus Application]

Ground and Test Device

SECTION 5:  INSPECTION & INSTALLATION

 DANGER

BEFORE PLACING THE GROUND AND TEST DEVICE IN SERVICE, CAREFULLY 

FOLLOW THE INSTALLATION PROCEDURE BELOW AND THE SAFE 

PRACTICES SET FORTH IN SECTION 2. NOT FOLLOWING THE PROCEDURE 

MAY RESULT IN INCORRECT G&T DEVICE OPERATION LEADING TO DEATH, 

BODILY INJURY, AND PROPERTY DAMAGE.

When the G&T device is first used and each time it is used in the 

future, it should be carefully examined and checked to make sure it 

is operating correctly.

5.1  EXAMINATION FOR DAMAGE

Examine the Ground and Test Device for loose or obviously damaged 

parts. Never attempt to install nor operate a damaged Ground and 

Test Device.

5.1.1  NAMEPLATE VERIFICATION

Verify the information on the new G&T device matches the 

information on the purchase order. If any discrepancies exist, 

notify Eaton’s Electrical Services & Systems for resolution prior to 

proceeding.

5.2  DEVICE AMPERAGE CONVERSION PROCEDURE

The primary circuit terminals of the Ground and Test Device consists 

of cycloaliphatic bushings with silver plated copper conductor 

‘knobs’. (Figure 3.3) Primary disconnecting contacts are attached 

to the knobs; these primary disconnects are configured to engage 

the circuit breaker compartment primary disconnects. It is critical 

to confirm that 1200A primary disconnects are installed prior to 

insertion in 1200A circuit breaker compartments; likewise for tests 

in 2000A circuit breaker compartments. THIS CONVERSION ALSO 

REQUIRES A CODE PLATE CHANGE PRIOR TO RACKING THE G&T 

INTO ITS CIRCUIT BREAKER COMPARTMENT. Follow the procedure 

below to convert from one primary current design to the other.
a.  Move the Ground and Test Device to an appropriate work area. It 

must not be inside the switchgear circuit breaker compartment 

when this procedure is performed. 

ote:

N

The primary disconnects of the G&T are stamped with the circuit 

breaker stationary primary disconnect they are designed to fit; 1200A or 

2000A.

b.  Remove the existing primary disconnects installed on the G&T 

using only the bushing wrench (Figure 3.3.c) provided. Any other 

wrench could damage the primary disconnect knobs; they should 

be avoided. (Figure 5.1)

Figure 5.1. Removing Bushing Knob

Figure 5.2. Bushing Knob Storage Area  

 

 

(AM4.16 250 G&T Shown)

Figure 5.3. Bushing Knob Storage Area  

 

 

(AM13.8 G&T Cable Type Device Shown)

Figure 5.4. Code Plate (AM4.16 250 G&T Shown)

Содержание AM-4.16-GT

Страница 1: ...er 2016 Effective September 2017 AM 13 8 GT Ground and Test Device Cable or Hard Bus Type Device Available Cable Type Device Shown AM 4 16 GT Ground and Test Device Hard Bus Type Device GE AM Cable or...

Страница 2: ...ffice should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eato...

Страница 3: ...SHINGS AND DISCONNECTING CONTACT ASSEMBLIES 17 4 3 INTERLOCKS 17 4 4 GROUNDING CONTACTS 17 SECTION 5 INSPECTION INSTALLATION 18 5 1 EXAMINATION FOR DAMAGE 18 5 1 1 NAMEPLATE VERIFICATION 18 5 2 DEVICE...

Страница 4: ...HIS DEVICE MUST BE DEVELOPED BY THE USER WARNING SATISFACTORY PERFORMANCE OF THESE GROUND AND TEST DEVICES IS CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INST...

Страница 5: ...r Hard Bus Application Ground and Test Device Table 2 GE AM 4 16 Ground and Test Device Dimensions Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps...

Страница 6: ...or Hard Bus Application Ground and Test Device Table 3 GE AM 4 16 Ground and Test Device Dimensions Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amp...

Страница 7: ...and Test Device Table 4 GE AM 13 8 Ground and Test Device Dimensions Cable or Hard Bus Application G T Device Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps A B C D E AM 13 8 12...

Страница 8: ...enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the Ground and Test Device in an...

Страница 9: ...s and to the ground connections provided on the G T device Grounding Shorting Bars If applicable AM 4 16 Style 94G2105H29 AM 13 8 Style 94G2100H30 Three grounding shorting bars are furnished only on h...

Страница 10: ...8 500 Cable Type Device 1200 2000 810 13 8 500 1200 830 13 8 750T Cable Type Device Single Terminal Set 1200 2000 935 Note N All G T devices listed in this table are hard bus type dual terminal devic...

Страница 11: ...est Device Figure 3 3 a Front External View of GE AM 4 16 250 G T Device Hard Bus Type Device 1 8 7 3 4 6 5 9 2 Front External View 1 Primary Disconnects 4 Bushing Knob Holder 7 Grounding Cable 2 Code...

Страница 12: ...eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 b Rear External View of GE AM 4 16 250 G T Device Hard Bus Type Device Rear External View 1 Lifting Points 3 Ground Con...

Страница 13: ...www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Front External View 1 Primary Disconnects 3 Lock Out 2 Code Plate 4 Kirk Key Interlock Figure 3 3 c Front External View of GE A...

Страница 14: ...N September 2017 www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 d Rear External View of GE AM 13 8 G T Device Hard Bus Type Device Rear External View 1 Lifting Poi...

Страница 15: ...e or Hard Bus Application Ground and Test Device Front External View 1 Primary Disconnects 3 Code Plate 5 Grounding Cable 2 Lock Out 4 Kirk Key Interlock 6 Cable Grounding Connection Figure 3 3 e Fron...

Страница 16: ...N September 2017 www eaton com GE AM Cable or Hard Bus Application Ground and Test Device Figure 3 3 f Rear External View of GE AM 13 8 G T Device Cable Type Device Rear External View 1 Lifting Points...

Страница 17: ...Ground and Test Device consist of six silver plated conductors Solid Stab type primary disconnecting contacts at the ends of the conductors provide means for connecting and disconnecting the G T devi...

Страница 18: ...s with silver plated copper conductor knobs Figure 3 3 Primary disconnecting contacts are attached to the knobs these primary disconnects are configured to engage the circuit breaker compartment prima...

Страница 19: ...e plate is located on the left hand side of the G T as one faces the device located approximately half way back approximately six inches from the floor Figure 5 4 Interference blocking is provided by...

Страница 20: ...bus bar Figure 3 1 e to the internal terminal corresponding to each phase Figure 5 8 Grounding bar can only be installed one way Take care to align the mounting bolts with the integral nut block behi...

Страница 21: ...ides of the circuit breaker compartment This is the disconnect position To elevate the G T device position the elevating control selector switch on the elevating motor to RAISE Engage the elevating mo...

Страница 22: ...ee cloth If a solvent is required to cut dirt use isopropyl alcohol Hardware Visually inspect all hardware Replace any damaged or missing hardware with parts equivalent to those provided with the Grou...

Страница 23: ...epending upon the service severity and continuity requirements Each customer should develop his own level based on operating experience 7 1 1 ORDERING INSTRUCTIONS Always specify the Ground and Test D...

Страница 24: ...vard Cleveland OH 44122 United States Eaton com 2017 Eaton All Rights Reserved Printed in USA Publication No IB182221EN September 2017 Eaton is a registered trademark All trademarks are property of th...

Отзывы: